800-2 Series Direct Vent Termination Kit(S) - kozy heat CALLAWAY 50 Installation And Operation Manual

Direct vent gas fireplace
Hide thumbs Also See for CALLAWAY 50:
Table of Contents

Advertisement

7.6 #800-2 Series Direct Vent
Termination Kit(s)
IMPORTANT: The horizontal heat shield must be installed when using a
45° elbow off of the fireplace back. See Section 7.7 on page 28.
IMPORTANT: The flex pipe is permanently attached to the exterior plate.
DO NOT ATTACH either #844-2 or #845-2 termination kit to fireplace (or
extension kit) until it has passed through the wall. Install termination
plates to the outside wall exterior.
IMPORTANT: The minimum bend radius to center is 6 in (152 mm)
required for installation of the flexible vent pipe. Care should be taken
when installing the flexible vent pipe to avoid a tight bend that may
cause abrasion or damage to the flexible pipe.
If terminating against vinyl siding, a vinyl siding protector must
be used (included with the #844-2 and #845-2 direct vent kits).
Follow instructions included.
Each #846-2 extension kit contains enough 5" & 8" flexible
aluminum pipe to extend chimney an additional 6 ft (1.83 m).
7.6.1 Assembly and Installation
1.
Mount the required wall thimble (G) with the required 3 in (76
mm) top clearance and 1 in (25 mm) side clearances to the
exterior wall, and seal.
2.
(OPTIONAL) insulate the wall-pass through with any unfaced
insulation products listed as non-combustible per ASTM E 136.
3.
Apply a liberal bead of exterior sealant around outer edge of
termination box (A), placing assembly through the wall-pass
through in exterior wall. Place screws through the four holes (B),
G
STAND-OFF HEAT SHIELDS
Figure 7.4, Installation and Assembly of #800-2 Series (Vent Heat Shield Assembly not shown for clarity purposes only)
#CLW-50 R.1 March 2018
securing it in place.
4.
Form the 5" & 8" flexible aluminum pipes on termination kit
(#844-2 or #845-2), and if applicable, on each extension kit.
5.
Gently pull 5" & 8" pipes down to the top of the fireplace, or if
applicable, the extension kit.
DO NOT stretch extension kit beyond 6 ft. (1.83 m); DO
NOT stretch beyond what is required. It is very difficult to
decompress flex pipes once stretched.
6.
Place a bead of sealant outside 5" flex pipe collar (C) (end with
EXTERNAL LIP) and sliding it into 5" pipe on extension kit or top
of fireplace (D). Secure with 3 evenly spaced screws.
7.
Place a bead of sealant inside 8" flex pipe collar (E) (end with
the INTERNAL lip), sliding it over 8" pipe on top of fireplace (F).
Secure with 3 evenly spaced screws.
8.
If additional extension kits are required, repeat Steps 4 and 5,
placing 5" & 8" pipes onto previous extension kit.
A
B
E
C
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
LEGEND
A
Termination box
B
Holes in exterior wall plate (only 3 shown)
C
5" flex pipe collar
D
5" pipe on fireplace or extension kit (not shown)
E
8" flex pipe collar
F
8" pipe on fireplace or extension kit (not shown)
G
Wall Pass-Through
VENTING 27