Horizontal Min. / Max. Venting Illustrations - kozy heat DASSEL DSL-36 Installation And Operation Manual

Table of Contents

Advertisement

NOTE: Page 22 has information on restrictor installation in conjunction with venting installation. Page 491 has information on restrictor
recommendations depending on burner flame appearance and instructions on installation after venting is completed.
MIN. / MAX. HORIZONTAL VENTING (5"x 8")
HORIZONTAL VENT
HEAT SHIELD
Figure 19a
IMPORTANT: The horizontal vent heat shield must be installed when using a 90-degree elbow to horizontally position the vent system.
Kozy Heat Wall Pass-thru, #800-WPT (4-1/2" (114mm) - 6-1/2" (165mm) wall thickness), or
#800-WPT2 (6-1/2" (165mm)-12-1/2" (318mm) wall thickness) must be used on all horizontal vent runs if using 5" x 8" venting.
If using Dura-Vent 8" x 6-5/8" Decreaser follow vent pipe manufacturer‟s installation instructions for their wall thimble.
MIN. / IMAX HORIZONTAL VENTING (8" x 6-5/8" DECREASER)
90° ELBOW
8" x 6-5/8" DECREASER
Figure 19b
VENTING
MINIMUM: 6in. (152mm)
MAXIMUM: 25ft. (7.62m); 30ft. (9.14m) when using stainless
steel pipe for entire length of termination.
90° ELBOW
MINIMUM: 6in. (152mm)
MAXIMUM: 25ft. (7.62m); 30ft. (9.14m) when using stainless steel pipe
for entire length of termination.
PAGE 19
TERMINATION CAP
TERMINATION CAP
2ft.
(610mm)