Specifications; Appliance Packaging Components; Heating Specifications - kozy heat CALLAWAY 50 Installation And Operation Manual

Direct vent gas fireplace
Hide thumbs Also See for CALLAWAY 50:
Table of Contents

Advertisement

2.0 SPECIFICATIONS

2.1 Appliance Packaging Components

Part Number
Description
CW50-150
Control Board Assembly
700-203
Manual Gas Shut-off Valve
CW50-057T
Glass Frame Assembly
900-086
5 in (127 mm) Restrictor Plate
700-408
Remote Control
CW50-SHD
Steel Framing
CW50-HHS
Vent Heat Shield Assembly
2.1.1 Additional Components Required
Refer to Section 7.0 Venting on page 22 for approved vent systems.

2.2 Heating Specifications

Natural Gas
Maximum
35,500 Btu/h
Input Rating
10.4 kW
Minimum
18,500 Btu/h
Input Rating
5.4 kW
Manifold Pressure
3.8" WC
(High)
(0.95 kPa)
Manifold Pressure
1.1" WC
(Low)
(0.27 kPa)
Orifice Size (DMS)
#34
2.2.1 Altitude Adjustment
This appliance may be installed at higher altitudes. Please refer to
National Fuel Gas Code ANSI Z223.1/NFPA 54, CSA-B149.1 Natural
Gas and Propane Installation Code, local authorities, or codes having
jurisdiction in you area regarding derate guidelines.
2.2.1.1 US Installations
Refer to the American Gas Association guidelines for the gas designed
appliances derating method. For elevations above 2,000 ft (610 m),
input ratings are to be reduced by 4% for each 1,000 ft (305 m) above
sea level.
2.2.1.2 Canadian Installations
When the appliance is installed at elevations above 4,500 ft (1,372 m),
the certified high altitude rating shall be reduced at the rate of 4% for
each additional 1,000 ft (305 m).v
8 SPECIFICATIONS
Propane
35,000 Btu/h
10.26 kW
18,000 Btu/h
5.2 kW
11" WC
(2.74 kPa)
2.9" WC
(0.72 kPa)
#51
Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces
#CLW-50 R.1 March 2018