7.8.2

Setting the damping value

Menu path:
"Configure_Pressure Measurement_Output"
Enter the desired value in the "Damping" line of the "Output parameter" field.
7.8.3

Correcting the zero shift

Menu path:
"Configure_Pressure Measurement_Process Variable"
Press the "Adjust" button in the "Zero shift" field.
Calibration is performed immediately and saved to the failsafe memory in the pressure
transmitter.
7.8.4

Setting the lower and upper range limit values

Menu path:
"Configure_Pressure Measurement_Process Variable"
The "Scaling" field offers two setting options:
1. Enter value
Enter the desired values in the "Lower Range Value" and/or "Upper Range Value" input fields.
2. Apply PV
For setting purposes, apply the pressure for the "Lower Range Value" and "Upper Range Value"
to the device. Make sure that the measuring limits are not exceeded.
Reducing stations with adjustable pressure and reference displays can be used as pressure
generators.
When making the connection, please ensure that there are no residual fluids (for gaseous
testing materials) or air bubbles (for fluid testing materials) in the connection lines, since these
can lead to errors during inspection.
The measurement deviation for the pressure generator should be at least three times smaller
than the desired measurement deviation for the pressure transmitter.
IM/265Gx/Ax-EN-07
265Gx, 265Ax
Configuration
65