5.2
Electrical connection in the cable connection area
Fig. 7: Cable connection area
1 Screw terminals for 0.5 ... 2.5 mm
(AWG 20 ... AWG 14) wire
2 Test terminals for 4 ... 20 mA (not with
Fieldbus transmitters)
3 Test
4 Cable entry (e.g., via M20 x 1.5)
The electrical connection is established in the connection area. The housing cover must be
unscrewed for this purpose.
The M20 x 1.5 cable glands, which are supplied by the manufacturer, are screwed only loosely
into the electronics housing. In order to achieve protection type IP 67, the glands must be
screwed in using a suitable tool (hexagon head, SW 22) until they are hand-tight.
IM/265Gx/Ax-EN-07
4
Test Signal
3
2
1
2
-
265Gx, 265Ax
Electrical connections
5
6
7
8
9
5 Ex d locking screw
6 Grounding/equipotential bonding terminal
7 Signal
8 Output signal/operating voltage
9 Grounding/equipotential bonding terminal
M00037
29