Electrical Installation
Terminal
12, 13
18
19
32
33
27
29
20
5
5
37
39
42
50
53
54
55
61
68 (+)
69 (-)
01, 02, 03
04, 05, 06
Table 5.14 Terminal Description
Extra terminals:
Two form C relay outputs. Location of the outputs depends on frequency converter configuration.
Terminals on built-in optional equipment. See the manual provided with the equipment option.
34
®
VLT
Parallel Drive Modules
Parameter
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-11 Terminal 19 Digital Input
Parameter 5-14 Terminal 32 Digital Input
Parameter 5-15 Terminal 33 Digital Input
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-13 Terminal 29 Digital Input
Analog inputs/outputs
Parameter 6-50 Terminal 42 Output
Parameter group 6-1* Analog Input 1
Parameter group 6-2* Analog Input 2
Parameter group 8-3 FC Port Settings
Parameter group 8-3 FC Port Settings
Parameter 5-40 Function Relay [0]
Parameter 5-40 Function Relay [1]
Danfoss A/S © 08/2017 All rights reserved.
Default
setting
Digital inputs/outputs
+24 V DC
[8] Start
[10] Reversing
[0] No operation
[0] No operation
[2] Coast inverse
[14] Jog
Safe Torque Off (STO)
Speed 0 – high limit
+10 V DC
Reference
Feedback
Serial communication
Relays
[9] Alarm
[5] Running
Description
Digital inputs. 24 V DC supply
voltage. Maximum output current
is 200 mA total for all 24 V loads.
Usable for digital inputs and
external transducers.
Selectable for digital input and
output. Default setting is input.
Common for digital inputs and 0 V
potential for 24 V supply.
Safe input (optional). Used for STO.
Common for analog output
Programmable analog output. The
analog signal is 0–20 mA or 4–
20 mA at a maximum of 500 Ω
10 V DC analog supply voltage.
15 mA maximum commonly used
for potentiometer or thermistor.
Analog input. Selectable for
voltage or current. Switches A53
and A54 select mA or V.
Common for analog input
Integrated RC-filter for cable shield.
ONLY for connecting the shield
when experiencing EMC problems.
RS485 Interface. A control card
switch is provided for termination
resistance.
Form C relay output. Usable for AC
or DC voltage and resistive or
inductive loads.