Testing The Motor Operation - Danfoss VLT FC 102 Installation Manual

Parallel drive modules 250–1200 kw
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Initial Start-up

6.5 Testing the Motor Operation

1.
Press [Main Menu] twice on the LCP.
2.
Press the navigation keys and the [OK] key to
navigate to parameter group 1-** Load and Motor
and press [OK].
3.
Navigate to parameter 1-23 Motor Frequency and
enter the frequency from the motor nameplate.
4.
Navigate to parameter 1-23 Motor Frequency and
enter the current from the motor nameplate.
5.
Navigate to parameter 1-25 Motor Nominal Speed
and enter the speed from the motor nameplate.
6.
Press [Status] to return to the operational display.
6
6
7.
Press [Hand On].
8.
Press [
9.
Press [
10.
Press [Off].
44
VLT
] to accelerate the motor.
] to decelerate the motor.