Range Change - Ametek Drexelbrook Universal IV Quick Start Manual

Cut monitor model transmitters 2-wire rf admittance / capacitance level measurement system with hart protocol
Table of Contents

Advertisement

2.3

Range Change

• It is possible to reduce the span of an existing
calibration by lowering the % water URV on the Menu
Screen
• If the reduction in span is greater than 20-30% of range,
better accuracy can be achieved by changing the input/
output curve to a lower range
• To re-range the instrument it is necessary to select a
different input curve. This procedure can be performed
on an installed instrument or in the shop with the
electronic unit itself
Figure 2-3
Captures from Main Screen
13
Quick Start Guide