Universal IV - Level Measurement System
2.5
Calibration / Configuration via Display / Keypad (Continued)
"Fct 3.03
Input value in PF
(INPT #)
"
"Fct 3.04
Output value in water
cut%
(OUT #)"
"Fct 4.00
Output
(OUTPUT)"
"Fct 4.01
Lower Range Value
(LRV)"
"Fct 4.02
Upper Range Value
(URV)"
"Fct 4.03
Damping in Seconds
(DAMPING)"
"Fct 4.04
4mA Trim
(TRIM 4)"
"Fct 4.05
20mA Trim
(TRIM 20)"
"Fct 4.06
Fixed Output
(LOCK mA)"
"Fct 4.07
Device ID
(POLL)"
"Fct 5.00
Display (DISPLAY)"
"Fct 5.01
Toggle the display
(TOGGLE?)"
"Fct 5.02
Water Cut (H2O)"
"Fct 5.03
Capacitance (CAP)"
"Fct 5.04
Calculated current (4--20)"
"Fct 6.00
Service (SERVICE)"
Value in PF
Value in % water
0.0 (Default)
80.0 (Default)
0.0 (Default)
4.00 (Default)
20.00 (Default)
0.00 (Default)
0 (Default)
NO (Default)
ENABLE (Default)
DISABLE (Default)
DISABLE (Default)
Enter the capacitance value in pF
Enter the cut value associate with the
capacitance in pF and point index. Repeat
FCT 3.02 to FCT 3.04 until all points are
entered in the strapping table
Configure the output from the unit including
LRV, URV, damping and fixed output
Enter the lower range value in % water
equivalent to 4mA output
Enter the upper range value in % water
equivalent to 20mA output
Enter damping in seconds to delay and filter
(software RC filter) the output in case of rapid
water cut variations
Use this menu to calibrate the 4 mA output
which is not common practice. Requires
calibrated meter to measure actual current
output
Use this menu to calibrate the 20 mA output
which is not common practice. Requires
calibrated meter to measure actual current
output
Use this menu to fix the output to a certain
mA value regardless of the measurement.
Enter the value in mA. The output will stay at
this value until exiting the menu of if display
times out in approx. 30 seconds
Enter the device ID to be used on the HART
loop. Each device on the loop must have a
unique device ID. Change only for multi-drop
configuration
Setup the parameter(s) to be displayed on the
unit during operation
Toggle between enabled parameters. YES or
NO
Enable or disable water cut measurement
display
Enable or disable capacitance measurement
in pF
Enable or disable the calculated current output
Use this menu for troubleshooting and service
16