Programming; Parameters - Operation And Display - Danfoss VLT 5000 Series Operating Instructions Manual

Frequency converters
Hide thumbs Also See for VLT 5000 Series:
Table of Contents

Advertisement

Parameters - Operation and Display

001 Language
(LANGUAGE)
Value:
English (ENGLISH)
German (DEUTSCH)
French (FRANCAIS)
Danish (DANSK)
Spanish (ESPAÑOL)
Italian (ITALIANO)
Function:
The choice in this parameter defines the language
to be used on the display.
Description of choice:
There is a choice of English [0], German [1], French
[2], Danish [3], Spanish [4] and Italian [5].
002 Local/remote control
(OPERATION SITE)
Value:
Remote control (REMOTE)
Local control (LOCAL)
Function:
There is a choice of two methods of controlling
the frequency converter.
Description of choice:
If Remote control [0] is selected, the frequency
converter can be controlled via:
1. The control terminals or the serial
communication port.
2. The [START] key. However, this cannot overrule
Stop commands (also start-disable) entered via the
digital inputs or the serial communication port.
3. The [STOP], [JOG] and [RESET] keys, provided that
these are active (see parameter 014, 015 and 017).
If Local control [1] is selected, the frequency
converter can be controlled via:
1. The [START] key. However, this cannot override
Stop commands on the digital terminals (if [2] or
[4] has been selected in parameter 013).
2. The [STOP], [JOG] and [RESET] keys, provided that
these are active (see parameter 014, 015 and 017).
3. The [FWD/REV] key, provided that this has been
activated in parameter 016 and that in parameter
013 a choice of [1] or [3] has been made.
4. Via P003 the local reference can be controlled by
means of the "Arrow up" and "Arrow down" keys.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
VLT
5. An external control command that can be connected
to terminal 16, 17, 19, 27, 29, 32 or 33. However,
[2] or [4] must be selected in parameter 013.
See also section Shift between local and remote control.
[0]
[1]
003 Local reference
[2]
(LOCAL REFERENCE)
[3]
Value:
[4]
Par 013 set for [1] or [2]:
[5]
0 - f
MAX
Par 013 set for [3] or [4] and par. 203 = [0] set for:
Ref
- Ref
MIN
MAX
Function:
This parameter allows manual setting of the
desired reference value (speed or reference for
the selected configuration, depending on the
choice made in parameter 013).
The unit follows the configuration selected in parameter
100, provided Process control, closed loop [3] or
Torque control, open loop [4] has been selected.
[0]
[1]
Description of choice:
Local [1] must be selected in parameter 002
for this parameter to be used.
The set value is saved in the case of a voltage
drop-out, see parameter 019.
In this parameter Data Change Mode is not exited
automatically (after time out).
Local reference cannot be set via the serial
communication port.
Warning: Since the value set is remembered
after the power has been cut, the motor
may start without warning when the
power is reinstated; if parameter 019 is changed
to Auto restart, use saved ref. [0].
004 Active Setup
(ACTIVE SETUP)
Value:
Factory Setup (FACTORY SETUP)
Setup 1 (SETUP 1)
Setup 2 (SETUP 2)
Setup 3 (SETUP 3)
Setup 4 (SETUP 4)
MultiSetup (MULTI SETUP)
®
5000 Series
50 Hz
0.0
[0]
[1]
[2]
[3]
[4]
[5]
97

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents