Electrical installation
Conversion of analogue inputs
Current input signal to voltage input
0-20 mA
0-10 V
4-20 mA
2-10 V
56
®
VLT
Connect 510 ohms resistor between input terminal 53 and 55
(terminal 54 and 55) and adjust minimum and maximum values in
parameters 309 and 310 (parameters 312 and 313).
MG.51.A9.02 - VLT is a registered Danfoss trademark
5000 Series