Procedure for initializing:
1. Select Initialisation.
2. Press the [OK] key.
3. Cut off the mains supply and wait for the
light in the display to go out.
4. Connect to mains.
Manual initialisation can be carried out by holding down
three keys at the same time as the mains voltage is
connected. Manual initialisation sets all parameters to
Parameter no.
621
622
623
624
625
626
627
628
629
630
631
Function:
The key data of the unit can be read out via the
display or the serial communication port.
Description of choice:
VLT type, parameter 621:
VLT Type indicates the unit size and basic
function concerned.
For example: VLT 5008 380-500 V.
Power section, parameter 622:
The power section states the given power
section being used.
For example: Extended with brake.
VLT ordering number, parameter 623:
Ordering number gives the ordering number
of the VLT type in question.
For example: 175Z0072.
Software version number, parameter 624:
Software version gives the version number.
For example: V 3,10.
LCP identification number, parameter 625:
The key data of the unit can be read out via the
display or the serial communication port.
For example:ID 1,42 2 kB.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
Description
Nameplate
VLT type
Power section
VLT ordering number
Software version number
LCP identification number
Database identification number
Power section identification number
Application option type
Application option ordering number
Communication option type
Communication option ordering number
®
VLT
5000 Series
the factory setting, except 600-605. The procedure
for manual initialisation is as follows:
1. Disconnect the mains voltage and wait for the
light in the display to disappear.
2. Hold down [DISPLAY/STATUS]+[MENU]+[OK] while
at the same time connecting the mains supply. The
display will now read MANUAL INITIALIZE.
3. When the display reads UNIT READY, the frequency
converter has been initialized.
(VLT TYPE)
(POWER SECTION)
(VLT ORDERING NO)
(SOFTWARE VERSION)
(LCP ID NO)
(PARAM DB ID)
(POWER UNIT DB ID)
(APP. OPTION)
(APP. ORDER NO)
(COM. OPTION)
(COM. ORDER NO)
Database identification number, parameter 626:
The key data of the unit can be read out via the
display or the serial communication port.
For example: ID 1,14.
Power section identification number,
parameter 627:
The key data of the unit can be read out via the
display or the serial communication port.
For example: ID 1,15.
Application option type, parameter 628:
This gives the type of application options fitted
with the frequency converter.
Application option ordering number,
parameter 629:
This gives the ordering number for the
application option.
Communication option type, parameter 630:
This gives the type of communication options
fitted with the frequency converter
Communication option ordering number,
parameter 631:
This gives the ordering number for the
communication option.
Display text
161