423 U 1 voltage
(U1 VOLTAGE)
Value:
0.0 - U
VLT,MAX
Function:
This parameter sets the Y-value of the 1st break point.
Description of choice:
Set the voltage desired at the F1 frequency
set in parameter 424.
See drawing for parameter 422.
424 F 1 frequency
(F1 FREQUENCY)
Value:
0.0 - par. 426
Function:
This parameter sets the X-value of the 1st break point.
Description of choice:
Set the frequency desired at the U1 voltage
set in parameter 423.
See drawing for parameter 422.
425 U 2 voltage
(U2 VOLTAGE)
Value:
0.0 - U
VLT, MAX
Function:
This parameter sets the Y-value of the 2nd break point.
Description of choice:
Set the voltage desired at the F2 frequency
set in parameter 426.
See drawing for parameter 422.
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.51.A9.02 - VLT is a registered Danfoss trademark
Factory setting of par. 103
Factory setting of par. 104
Factory setting of par. 103
®
VLT
5000 Series
426 F 2 frequency
(F2 FREQUENCY)
Value:
par. 424 - par. 428
Function:
This parameter sets the X-value of the 2nd break point.
Description of choice:
Set the frequency desired at the U2 voltage
set in parameter 425.
See drawing for parameter 422.
427 U 3 voltage
(U3 VOLTAGE)
Value:
0.0 - U
VLT,MAX
Function:
This parameter sets the Y-value of the 3rd break point.
Description of choice:
Set the voltage desired at the F3 frequency
set in parameter 428.
See drawing for parameter 422.
428 F 3 frequency
(F3 FREQUENCY)
Value:
par. 426 - par. 430
Function:
This parameter sets the X-value of the 3rd break point.
Description of choice:
Set the frequency desired at the U3 voltage
set in parameter 427.
See drawing for parameter 422.
429 U 4 voltage
(U4 VOLTAGE)
Value:
0.0 - U
VLT,MAX
Function:
This parameter sets the Y-value of the 4th break point.
Description of choice:
Set the voltage desired at the F4 frequency
set in parameter 430.
Factory setting of par. 104
Factory setting of par. 103
Factory setting of par. 104
Factory setting of par. 103