Alarm, fault and system messages
12.1 Representation of system messages on the digital display
12.1.2
System messages during initialization
Remarks about the tables:
nn
/
Messages during initialization
Message
Line
Up
Down
P--
X
RUN1
X
RUN2
X
RUN3
X
RUN4
X
RUN5
X
YEND1
X
YEND2
X
RANGE
X
218
stands for variable numeric values
Error symbol
(Slash): texts to the left and the right of the slash blink alternately
Meaning / cause
Measuring range was exceeded, the
potentiometer is in the inactive zone, the
transmission ratio selectors or the effective
lever arm are not adjusted as per the
actuator travel
Initialization was started, part 1 is active (the
direction of action is determined)
Initialization part 2 is active (actuator travel
check and determination of end stops)
Initialization part 3 is active (determination
and display of actuating times)
Initialization part 4 is active (determination of
the minimum controller increment length)
Initialization part 5 is active (optimization of
the transient response)
The first end position can be approached
only in case of a manual initialization
The second end position can be approached
only in case of a manual initialization
The end position or the measuring span is
beyond the permissible range only in case of
a manual initialization
Measure
Switch the transmission ratio selector to
•
90° especially in case of part-turn
actuators
Adjust the effective lever length of linear
•
actuators as per the measuring range
Wait
•
Wait
•
Wait
•
Wait
•
Wait until "FINSH" is displayed
•
(initialization completed successfully)
Acknowledge by pressing the operating
•
mode button slightly and exit the
configuration level by pressing it longer
Approach the first end position using the
•
"+" or "-" button
Acknowledge using the operating mode
•
button
Approach the second end position using
•
the "+" or "-" button
Acknowledge using the operating mode
•
button
Approach another end position using the
•
"+" and "-" buttons and acknowledge with
the operating mode button, or
Move the friction clutch until "ok" is
•
displayed, and then acknowledge with
the operating mode button, or
Terminate the initialization process by
•
pressing the operating mode button,
switch to the P-manual mode and correct
the actuator travel and the position
displacement sensor
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07