Troubleshooting

8.2 Info IDs, error messages and corrective measures

8.2
Info IDs, error messages and corrective measures
The following table shows the IDs of diagnostic messages and possible causes and
instructions for corrective actions.
Messages on the Display (Page 21)
ID
Symbol
Status line
6A
-
6C
NO INIT + set‐
point as percent‐
age
6d
-
6E
-
6F
-
6H
-
6L
-
-
6N
-
6P
-
6r
-
32
Meaning / cause
● Initialization errors
● Insufficient supply of compressed
air
● Mounting kit not correctly mounted
● Valve blocked
Positioner is not initialized
● Measuring range of position
detection exceeded
● Swivel area of the valve is larger
than 110°
● Positioner installed on a different
actuator without re-initialization.
● End positions of valve are worn
Maintain valve position is activated
through digital input (DI). Setting in
parameter "DIGITAL IN" [21]
Approach valve position is activated
through digital input (DI). Setting in
parameter "CLOSE LIMIT" [30]
Approach valve position is activated
through digital input (DI). Setting in
parameter "OPEN LIMIT" [32]
Digital input (DI) is activated. This sta‐
tus is reported via the digital output
(DO).
Setting in parameter "BEHAVIOR
DI[22]>MSG"
● Maximum angle span exceeded
● Effective lever arm is not adjusted
to the actuator travel
● Mounting kit not correctly mounted
● Value below minimum angle span
● Effective lever arm is not adjusted
to the actuator travel
● Mounting kit not correctly mounted
A pneumatic leakage is present
Remedy
Eliminate the cause. Start the initialization
process.
Start the initialization with
Check the mounting kit and the wear. Start
the initialization process.
Configured response. Change the parame‐
ters until the message no longer appears.
Configured response. Change the parame‐
ters until the message no longer appears.
Configured response. Change the parame‐
ters until the message no longer appears.
Not necessary.
Position the carrier pin at a larger stroke
value.
Check the mounting kit.
Use the electropneumatic positioner SI‐
PART PS2 from Siemens with a swivel
area of 185° (special version).
Position the carrier pin at a smaller stroke
value.
Check the mounting kit.
Remedy the pneumatic leak of the actuator
and the piping.