10.2.2.16 Description of parameter 46

46. STRK - limit for monitoring the path integral (number of strokes)
Use this parameter to set the limit for the path integral. This parameter corresponds to the
profile parameter "TOTAL_VALVE_TRAVEL_LIMIT".
NOTICE
Limit overshoot
A fault message is not triggered if the set limit is exceeded. Only the
"CB_TOT_VALVE_TRAV" bit in the "CHECK_BACK" parameter is set.
The fault message is activated if the path integral exceeds the limit.
This function enables preventive maintenance of the control valve.
Note
Path integral
Use the "L" parameter in the advanced diagnostics to monitor the path integral along with the
diagnostics messages.
The factory setting is "1E9".

10.2.2.17 Description of parameter 47

47.PRST - Preset
Use this parameter to reset the factory setting. Press the
seconds. Not all parameters are set to the factory setting if "no" is shown on the digital
display. All parameters are set to the factory setting if "oCAY" is shown on the digital display.
Note
After a "Preset", the positioner must be re-initialized. All maintenance parameters
determined until now are deleted.
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
Parameter assignment/Addressing
10.2 Description of parameters
increment button for at least 5
155