Siemens SIPART PS2 PA 6DR55 Series Operating Instructions Manual page 152

Electropneumatic positioner
Table of Contents

Advertisement

Parameter assignment/Addressing
10.2 Description of parameters
Note that:
● Both limits can be evaluated separately in the control system only for settings 1 or 4 since
● The response of both limits cannot be detected in the "READBACK" and "POS_D" status
● The direction of action shown reverses for an alarm unit.
● The direction of action also reverses when the setting of the response threshold of alarms
● The hysteresis of the limit is 1% by default.
● In the factory setting "OFF", the output of both alarms "41.A1" and "42.A2" is deactivated.
The factory setting is "OFF".
See also
Description of parameter 34 (Page 148)
152
both the limits, A1 and A2 are connected to each other through a logical OR combination
in the "READBACK" and "POS_D" status messages.
reports if the positioner is in the manual mode.
in the "41.A1" parameter is greater than that in the "42.A2" parameter.
Direction of action and hysteresis
Operating Instructions, 09/2007, A5E00127926-07
A1 = 52
AFCT = MIN / MAX
A2 = 48
Path = 45
Active
Path = 50
Active
Path = 55
A1 = 52
AFCT = -MIN / -MAX
A2 = 48
Path = 45
Path = 50
Path = 55
Active
SIPART PS2 with PROFIBUS communication
Active
Active
Active