Setting the actuator
1. Check whether the mechanical unit can be moved freely in the entire actuating range.
2. Now move the actuator to the horizontal position of the lever.
3. A value between "P48.0" and "P52.0" is shown on the display.
4. If a value beyond this value range is shown on the display, you must move the friction
9.3.2

Automatic initialization of linear actuators

Conditions
The following conditions must be fulfilled before activating the automatic initialization:
1. The actuator spindle can be moved completely.
2. The actuator spindle is at a central position after moving.
Initializing the positioner automatically
Note
An ongoing initialization can be interrupted at any time. Press the
for this purpose. The settings configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset
settings in the "PRST" parameter.
1. Switch to the "Configuration" mode. Keep the operating modes buttons pressed for more
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
Move the actuator to the respective end position using the
the direction buttons simultaneously to reach the end position faster.
clutch. Move the friction clutch until a value between "P48.0" and "P52.0" is achieved.
The closer the value is to "P50.0", the more accurate is the stroke travel determined by
the positioner.
NOTICE
The following is applicable for the flameproof enclosure version:
The inner friction clutch is fixed. Therefore, only move the outer friction clutch.
than 5 s for this purpose. The following is shown on the digital display:
9.3 Commissioning the linear actuators
and
buttons. Press both
operating mode button
Commissioning
123