Preparing for operation

3.6.2 Automatic initialization of linear actuator

.
76
NOTICE
for the explosion proof version:
Only adjust the outer friction clutch (8, Fig. 9, page 26). The internal
friction clutch (9, Fig. 8 page 25) is fixed and, for the explosion proof
version, must not be adjusted.
If you can move the actuator correctly, leave it standing in a central
position and start automatic initialization:
1.
Press the operation mode key
you to the Configuration operating mode.
Display:
2.
Switch to the second parameter by pressing the operation mode
key
briefly.
Display:
NOTE
It is vital that this value corresponds to the setting of the transmission
ratio selector (8, figure 8, page 25) (33° or 90°).
3.
Switch on to the following display with the operation mode key
You only need to set this parameter if you want to have the total
stroke in mm displayed at the end of the initialization phase. To do
this, select the same value in the display to which you have set the
carrier pin to the scale on the lever.
for longer than 5 s. This brings
or
SIPART PS2 PA Manual
A5E00127926--05
: