10.2.2.11 Description of parameter 40

40.AFCT - alarm function
Six setting options are available:
1. Min Max
2. Min Min
3. Max Max
4. -Min -Max (inverting message)
5. -Min -Min (inverting message)
6. -Max -Max (inverting message)
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07
If the binary input is activated, the actuator uses the value defined by "YA" and "YE" for
controlling in the "Automatic" mode.
In "Automatic" operating mode the piezo valves are blocked when the binary input is
activated. The actuator remains in the last position. Leakage measurements can then be
taken without the initialization function.
Binary inputs 1 or 2 can be used to initiate a partial stroke test by pressing either a
normally closed or a normally open contact depending on the choice.
No function
Direction of action and hysteresis
Parameter assignment/Addressing
10.2 Description of parameters
Alarm unit
Examples:
A1
A1 = 48
AFCT = MIN / MAX
A2 = 52
Path = 45
Active
Path = 50
Path = 55
A1 = 48
AFCT = -MIN / -MAX
A2 = 52
Path = 45
Path = 50
Active
Path = 55
Active
A2
Active
Active
Active