10.2.3.12 Description Of Parameter P - Siemens SIPART PS2 PA 6DR55 Series Operating Instructions Manual

Electropneumatic positioner
Table of Contents

Advertisement

Parameter assignment/Addressing
10.2 Description of parameters
The factory setting is "2.0".
O4.FACT3 - factor 3
Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in
a range from "0.1" to "40.0". The limit threshold is the product of "O1.LIMIT" and
"O4.FACT3".
The threshold 3 fault message is displayed when the limit threshold 3 exceeds. The process
to activate and display this fault message is described in the "XDIAG" parameter.
The factory setting is "5.0".

10.2.3.12 Description of parameter P

P. PAVG - calculation of position average
Use this parameter to activate the test to calculate and monitor the position average.
Configure the following settings to activate the test:
1. Set the "P. PAVG" parameter to "On". Sub-parameters to set the test parameters are
displayed. The test is activated.
2. Set the suitable parameter values in sub-parameters. The setting options available in
sub-parameters are described below.
During the test, the position and reference average values are always compared at the end
of a time interval. The positioner triggers a fault message if the current position average
exceeds a threshold.
The factory setting is "OFF".
P1.TBASE - time base for averaging
Use this sub-parameter to set the time interval to calculate the position average.
The following values are available to define the time intervals:
● 30 minutes
● 8 hours
● 5 days
● 60 days
● 2.5 years
After starting the reference average calculation and the expiry of the time interval, a position
average over the interval period is determined and compared with the reference average.
The test is then restarted.
The factory setting is "0.5 h".
174
SIPART PS2 with PROFIBUS communication
Operating Instructions, 09/2007, A5E00127926-07