Siemens SIPART PS2 PA 6DR55 Series Operating Instructions Manual

Siemens SIPART PS2 PA 6DR55 Series Operating Instructions Manual

Electropneumatic positioner
Table of Contents

Advertisement

Quick Links

Operating Instructions Edition 09/2007
Electropneumatic Positioner
SIPART PS2 PA
6DR55xx
sipart
p

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIPART PS2 PA 6DR55 Series

  • Page 1 Operating Instructions Edition 09/2007 Electropneumatic Positioner SIPART PS2 PA 6DR55xx sipart...
  • Page 3 Introduction General safety notes Description SIPART Installation Electropneumatic positioner Installing the optional SIPART PS2 with PROFIBUS modules communication Connect Operating Instructions Operation Functional safety Commissioning Parameter assignment/Addressing Functions/operations using PROFIBUS PA Alarm, fault and system messages Service and maintenance Technical data Dimension drawings 6DR55** Scope of delivery/spare...
  • Page 4 Trademarks All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
  • Page 5: Table Of Contents

    Table of contents Introduction.............................. 11 Purpose of this document ......................11 History ............................11 Further information........................12 General safety notes..........................13 General information ........................13 Correct usage..........................13 Laws and directives ........................13 Measures .............................14 Qualified Personnel........................15 Description............................... 17 Function ............................17 Structure............................17 3.2.1 Design overview...........................17 3.2.2 Type plate structure ........................20 Operation with natural gas ......................21 3.3.1...
  • Page 6 Table of contents 3.6.6 Connection ..........................34 3.6.7 Number of connectable devices....................35 3.6.8 Assigning the device addresses ....................36 SIMATIC PDM..........................36 Installation ............................... 37 Safety notes for installation ......................37 Installing the linear actuator ......................38 Installing the part-turn actuator ....................43 Using the positioner in a humid environment................
  • Page 7 Table of contents 6.1.6.3 Binary inputs and outputs ......................80 6.1.6.4 SIA unit............................80 6.1.6.5 Mechanical limit switch module....................81 6.1.7 Connection for the "intrinsically safe" type of protection..............85 6.1.7.1 Standard controller........................85 6.1.7.2 Current output ..........................86 6.1.7.3 Binary inputs and outputs ......................87 6.1.7.4 SIA unit............................88 6.1.7.5 Mechanical limit switch module....................88...
  • Page 8 Table of contents Parameter assignment/Addressing ......................135 10.1 Overview of the parameters ...................... 135 10.1.1 Overview of parameters 1 to 5 ....................135 10.1.2 Overview of parameters 6 to 53....................136 10.1.3 Overview parameters A to P ..................... 139 10.2 Description of parameters ......................
  • Page 9 Table of contents 11.2.2.4 Update diagnostics status......................179 11.2.2.5 Set address ..........................179 11.2.2.6 Operation ...........................179 11.2.2.7 Simulation ..........................181 11.2.2.8 Partial stroke test (PST)......................182 11.2.2.9 PST trace characteristic......................183 11.2.2.10 Status monitoring ........................183 11.2.2.11 Initialization parameters ......................184 11.2.2.12 Initialization ..........................184 11.2.2.13 Reset PDM parameters ......................185 11.2.2.14 Reset the field device.........................185 11.2.2.15 Write lock ...........................186 11.2.3...
  • Page 10 Table of contents 12.4.1 Fault identification ........................236 12.4.2 Remedial measures table 1 ...................... 236 12.4.3 Remedial measures table 2 ...................... 237 12.4.4 Remedial measures table 3 ...................... 238 12.4.5 Remedial measures table 4 ...................... 238 12.4.6 Remedial measures table 5 ...................... 239 Service and maintenance ........................
  • Page 11: Introduction

    Introduction Purpose of this document This programming manual contains all information that you will require to commission and use the device. It is aimed at persons who install the device mechanically, connect it electrically, parameterize and commission it, as well as at service and maintenance engineers. This document also contains special information and safety notes that you will require when using an SIL-certified device in safety-instrumented systems.
  • Page 12: Further Information

    The contents of these instructions shall not become part of or modify any prior or existing agreement, commitment or legal relationship. All obligations on the part of Siemens AG are contained in the respective sales contract which also contains the complete and solely applicable warranty conditions.
  • Page 13: General Safety Notes

    General safety notes General information This device left the factory free from safety problems. In order to maintain this status and to ensure safe operation of the device, please observe the safety information and warnings contained in these instructions. Correct usage The device may only be used for the purposes specified in these instructions.
  • Page 14: Measures

    General safety notes 2.4 Measures Measures For the sake of safety, the following precautions must be observed: WARNING Type of protection "pressure-proof encapsulation" Devices with "pressure-proof encapsulation" protection may only be opened when off circuit. "Intrinsically safe" protection type "Intrinsically-safe" devices lose their certification as soon as they are operated on circuits which do not correspond with the test certification valid in their country.
  • Page 15: Qualified Personnel

    General safety notes 2.5 Qualified Personnel CAUTION Electrostatic Sensitive Devices (ESD) This device contains electrostatic sensitive devices. Electrostatic sensitive devices may be destroyed by voltages that are undetectable to a human. Voltages of this kind occur as soon as a component or an assembly is touched by a person who is not grounded against static electricity.
  • Page 16 General safety notes 2.5 Qualified Personnel SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 17: Description

    Description Function ● The electropneumatic positioner and an actuator form a control system. The current position of the actuator is recorded by a servo potentiometer and the actual value x is fed back. The setpoint and the actual value are simultaneously shown on the digital display. ●...
  • Page 18 Description 3.2 Structure The positioner is used to move and control pneumatic actuators. The positioner works electropneumatically; compressed air is used as an auxiliary power supply. The positioner is used to control valves with: ● Linear actuator ● Part-turn actuator VDI/VDE 3845 Difference attachment extensions are available for linear actuators: ●...
  • Page 19 Description 3.2 Structure Figure 3-2 Positioner attached to dual-action part-turn actuator ① Pressure gauge block, dual-action. ② Part-turn actuator ③ Dual-action positioner in plastic enclosure. Figure 3-3 Positioner in flameproof enclosure attached to linear actuator ① Single-action positioner in flameproof enclosure. ②...
  • Page 20: Type Plate Structure

    Ta = -30 ... 50/65/80°C Ta = -30 ... 50(T6)/65(T5)/80(T4) °C Uh= 9 ... 24V Install per Contr. Dwg. A5E00065622AA TÜV 00 ATEX 1654 Siemens AG, D-76181 Karlsruhe www.siemens.com/sipartps2 Made in France F-Nr. N1-P2 -12 3456789 F-Nr. N1-P2 -12 3456789 Type plate structure, example of the EEx ia/ib degree of protection ①...
  • Page 21: Operation With Natural Gas

    Description 3.3 Operation with natural gas Operation with natural gas 3.3.1 Safety notes for operation with natural gas When operating the positioner with natural gas, you must follow and adhere to the following safety notes: WARNING Operation with natural gas 1.
  • Page 22 Description 3.3 Operation with natural gas Maximum values for escaping natural gas Natural gas escapes parallel to the exhaust air outlet E: ● From the enclosure vent at the bottom side of the device ● From the control air outlet near the pneumatic connections This escaping natural gas cannot be collected and carried off.
  • Page 23: Device Components

    Description 3.4 Device components Device components 3.4.1 Overview of device components 90° Jumper Shut Down disabled Shut Down enabled Shut Down input Positioner Binary input 1 33° Figure 3-5 View of the positioner (cover open; plastic enclosure) ① Bus cable ⑩...
  • Page 24 Description 3.4 Device components Figure 3-6 View of the positioner in the flameproof enclosure ① Input: supply air ⑦ Restrictor Y1 ② Output: Actuating pressure Y1 ⑧ Restrictor Y2 ③ Digital display ⑨ Friction clutch adjustment wheel ④ Output: Actuating pressure Y2 ⑩...
  • Page 25: Motherboard

    Description 3.4 Device components 3.4.2 Motherboard Figure 3-7 Motherboard The motherboard contains: ● CPU ● Memory ● Analog-to-digital converter ● Digital display ● Buttons ● Terminal strips to connect the optional module to the motherboard 3.4.3 Electrical connections Connecting terminals of the standard controller, the I and the alarm optional module are provided at the left front edges, and are arranged in a staircase-shape.
  • Page 26: Pneumatic Connections

    Description 3.4 Device components 3.4.4 Pneumatic connections 3.4.4.1 Pneumatic connection on the standard controller Structure The pneumatic connections are provided on the right side of the positioner. Figure 3-9 Pneumatic connection on the standard controller ① Actuating pressure Y1 for single and double-acting actuators ②...
  • Page 27: Pneumatic Connection In The Flameproof Enclosure

    Description 3.4 Device components 3.4.4.2 Pneumatic connection in the flameproof enclosure Structure The pneumatic connections are provided on the right side of the positioner. Figure 3-10 Pneumatic connection in the flameproof enclosure ① Restrictor Y2 ⑤ Actuating pressure Y1 ② Restrictor Y1 ⑥...
  • Page 28 Description 3.4 Device components Figure 3-11 Regulating action of pneumatic connection SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 29: Purge Air Switching

    Description 3.4 Device components 3.4.5 Purge air switching Note Equipment Versions with flameproof enclosures are not equipped with purge air switching. When the enclosure is open, the purge air switch above the pneumatic terminal strip on the pneumatic block can be accessed. ●...
  • Page 30: Functional Principle

    Description 3.5 Functional principle Figure 3-13 Restrictors ① Restrictor Y1 ② Restrictor Y2, only in the version for double-acting actuators ③ Hexagon socket-head screw 2.5 mm Functional principle 3.5.1 Control system The electropneumatic positioner and an actuator form a control system. The current position of the actuator is recorded by a servo potentiometer and the actual value x is fed back.
  • Page 31: Pneumatic Actuator

    Description 3.5 Functional principle 3.5.3 Pneumatic actuator Pneumatic actuators are available in single and double-acting versions. Only one pressure chamber is ventilated and depressurized in case of a single-acting version. The pressure developed works against a spring. Two pressure chambers work against each other in case of a double-acting version.
  • Page 32: Profibus Pa

    Description 3.6 PROFIBUS PA PROFIBUS PA 3.6.1 Overview The Process Field Bus (PROFIBUS) is an open communication system for automation technology and is specified in the European standard EN 50170. PROFIBUS Process Automation (PROFIBUS PA) is a variant of PROFIBUS Decentral Peripherals (PROFIBUS DP), which is widely used in process technology.
  • Page 33: Properties

    Description 3.6 PROFIBUS PA Class-1 master Class-2 master (Klasse 1) PROFIBUS DP PROFIBUS PA Field devices, decentralized periphery, subordinate Controls, gateway to PROFIBUS PA Figure 3-15 Functional principle of the PROFIBUS automation system The figure shows a section of a typical PROFIBUS automation system. The control system consists of two masters with distributed tasks.
  • Page 34: Connection

    Description 3.6 PROFIBUS PA necessary basic information to find profile parameters. One parameterization tool serves all profile-conforming devices, regardless of type or manufacturer. Depending on the size of the installation (and therefore the number of field devices) and the time behavior required, you implement the system with one or more PROFIBUS PA strands. One PROFIBUS PA strand consists of the components shown in the following figure.
  • Page 35: Number Of Connectable Devices

    Description 3.6 PROFIBUS PA For reasons related to transmission technology, the bus is also equipped on the far end with a terminating resistance T. When using the recommended bus cable, the theoretical maximum cable length is 1900 meters. The theoretical maximum cable length is the sum of all cable segments.
  • Page 36: Assigning The Device Addresses

    The next positioner is then connected to the bus and processed the same way. We recommend writing the set address on the field device with a wipe resistant pen. See also Catalog process instrumentation (http://www.siemens.com/processinstrumentation/catalogs) SIMATIC PDM SIMATIC PDM is a software package for the configuration, paramaterization, commissioning, diagnostics, and servicing of the device and other process devices.
  • Page 37: Installation

    Installation Safety notes for installation WARNING Mechanical impact effect Protect the 6DR5**0-*G***-**** version of the positioner from mechanical impact effects that are greater than 1 Joule; this ensure adherence to the IP66 degree of protection. When installing, observe the following sequence imperatively to avoid injuries or mechanical damage to the positioner/mounting kit: 1.
  • Page 38: Installing The Linear Actuator

    Installation 4.2 Installing the linear actuator CAUTION Humid environment/dry compressed air Install the positioner in a humid environment such that the positioner shaft does not freeze at low ambient temperatures. Ensure that water does not seep through an open enclosure or an open gland. Water may seep through if the positioner is not installed and connected on-site immediately and finally.
  • Page 39 Installation 4.2 Installing the linear actuator 2. Slide the pick-up bracket ② into the notches of clamping pieces. Set the required length and tighten the bolts such that the pick-up bracket can still be moved. 3. Insert the pre-installed pin ④ in the lever ⑥. Install the lever with the washer ⑫ and the spring lock washer ⑭.
  • Page 40 Installation 4.2 Installing the linear actuator Assembly procedure: positioner with linear actuator Assembly procedure: linear actuator without flameproof enclosure SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 41 Installation 4.2 Installing the linear actuator Assembly procedure: positioner with linear actuator Assembly procedure: linear actuator with flameproof enclosure Mounting on the yoke with plane surface Mounting on the yoke with fin Mounting on the yoke with columns SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 42 Installation 4.2 Installing the linear actuator "Linear actuator IEC 534 (3 mm to 35 mm)" mounting kit 6DR4004-8V and 6DR4004-8L Sr. No. Quantity Name Note ① NAMUR mounting bracket Standardized connection point for mount with fin, column or plane IEC 534 surface ②...
  • Page 43: Installing The Part-Turn Actuator

    Installation 4.3 Installing the part-turn actuator Installing the part-turn actuator Conditions You require an actuator-specific VDI/VDE 3845 mount to install the positioner on a part-turn actuator. The mount and the bolts are included in the scope of delivery of the corresponding actuator.
  • Page 44 Installation 4.3 Installing the part-turn actuator Assembly procedure for the positioner with part-turn actuator SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 45 Installation 4.3 Installing the part-turn actuator Assembly procedure for the positioner with part-turn actuator and flameproof enclosure 0% 20 40 60 80 100% SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 46 Installation 4.3 Installing the part-turn actuator "Part-turn actuator" mounting kit 6DR4004–8D Sr. No. Quantit Name Note ② Coupling wheel Installation on the position feedback shaft of the positioner ③ Carrier Installation on the shaft stump of the actuator ④ Multiple plate Display of the actuator position, consists of scale ⑤...
  • Page 47 Installation 4.3 Installing the part-turn actuator Figure 4-1 Installed positioner for part-turn actuators ① Positioner ⑩ Feedback shaft ② Coupling wheel ⑭ Hexagon bolt - M6 x 12 ③ Carrier ⑮ Lock washer S6 ④ Part-turn actuator ⑯ Socket cap screw - M6 x 12 ⑤...
  • Page 48: Using The Positioner In A Humid Environment

    Installation 4.4 Using the positioner in a humid environment Ø35 (1.38) F05-Lkr.-Ø50 (1.97) Figure 4-2 Dimensions of mount (actuator-dependant) ① Fastening plane of positioner ② Part-turn actuator Using the positioner in a humid environment Introduction CAUTION Never clean the positioner with a high pressure cleaner since the IP66 degree of protection is not sufficient for this.
  • Page 49 Installation 4.4 Using the positioner in a humid environment Favorable and unfavorable mounting positions Avoid the unfavorable mounting positions: ● To prevent fluids seeping through during normal operation of the device, e.g. through exhaust air openings. ● Otherwise the digital display becomes poorly legible. Figure 4-3 Favorable and unfavorable mounting positions Additional measures to prevent liquids from seeping through...
  • Page 50: Notes For Using Positioners That Are Exposed To Strong Accelerations Or Vibrations

    Installation 4.5 Notes for using positioners that are exposed to strong accelerations or vibrations Procedure for installing the plastic hose on the gland 1. Unscrew the sintered bronze attenuator from the exhaust air opening at the bottom side of the enclosure. 2.
  • Page 51: Setting The Friction Clutch

    Installation 4.6 Setting the friction clutch Setting the friction clutch Procedure NOTICE The following is applicable for the "flameproof enclosure" version: • Move only the outer friction clutch. The inner friction clutch is fixed and may not be moved in case of a flameproof enclosure. •...
  • Page 52: Switching The Transmission Ratio

    Installation 4.7 Switching the transmission ratio Switching the transmission ratio Procedure Lock the transmission ratio selector starting from the neutral position (condition at delivery) as follows: 1. Move the yellow wheel below the terminals using a commercially available, approximately 4 mm wide screwdriver anticlockwise or clockwise depending on the 33° or 90° position that you have selected until it noticeably engages.
  • Page 53: External Position Displacement Sensor

    Installation 4.8 External position displacement sensor External position displacement sensor WARNING Versions with flameproof enclosures may not be operated with an external position detection system. The aforementioned measures are not adequate in some applications. For example, continuous and strong vibrations, high or too low ambient temperatures and nuclear radiation.
  • Page 54 Installation 4.8 External position displacement sensor SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 55: Installing The Optional Modules

    Installing the optional modules General information about the installation of option modules 5.1.1 Safety notes for installing the option modules WARNING Assembling the components For the composition of the components it must be ensured that only positioners and option modules that are certified for the relevant operating range are combined. This condition applies in particular to the safe operation of the positioner in the areas of zone 1, 2 and 22, in which the atmosphere can be potentially explosive.
  • Page 56: Installing Optional Modules In The Standard And Intrinsically Safe Version

    Installing the optional modules 5.1 General information about the installation of option modules 5.1.2 Installing optional modules in the standard and intrinsically safe version The following optional modules are available for the positioner in the standard and intrinsically safe version: ●...
  • Page 57 Installing the optional modules 5.1 General information about the installation of option modules Overview image: installing the optional modules The following image will help you when installing the optional modules: Figure 5-1 Installing the optional modules ① Module cover ⑬ SIA unit or mechanical limit switch module ②...
  • Page 58: Installing The Optional Modules In The "Flameproof Enclosure" Version

    Installing the optional modules 5.1 General information about the installation of option modules ⑦ Friction clutch adjustment wheel Sign set ⑧ Actuating disc for A2, terminals 51 and 52 ⑲ Warning sign on the side opposite to the type plate ⑪...
  • Page 59 Installing the optional modules 5.1 General information about the installation of option modules Overview image: installing the optional modules The following image will help you when installing the optional modules: Figure 5-2 Installing the optional modules in a flameproof enclosure ①...
  • Page 60: Installing The Module Cover

    Installing the optional modules 5.1 General information about the installation of option modules 5.1.4 Installing the module cover Installing the module cover Note Untimely wear The module cover is fastened using self-tapping screws. You can prevent the module cover from wearing untimely by adhering to the installation instructions. Proceed as follows to install the module cover: 1.
  • Page 61: Iy Module

    Installing the optional modules 5.2 Iy module Iy module Function ● The optional I module indicates the current actuator position as a dual line signal with = 4 to 20 mA. The I module is potentially separated from the standard controller. Thanks to the dynamic control, this module can report the arising operational faults automatically.
  • Page 62: Alarm Unit

    Installing the optional modules 5.3 Alarm unit Alarm unit Function The alarm unit triggers fault messages and alarms using binary outputs. The message function is based on the change in the signal status: ● If the signal status is "HIGH", there is no alarm message and the binary inputs are conductive.
  • Page 63: Slotted Initiator Alarm Unit

    Installing the optional modules 5.4 Slotted initiator alarm unit Installation Proceed as follows to install the alarm unit: 1. Slide the alarm unit below the motherboard in the module rack. Ensure that you slide it up to the end stop. 2.
  • Page 64: Installing The Slotted Initiator Alarm Unit

    Installing the optional modules 5.4 Slotted initiator alarm unit Device features The slotted initiator alarm unit, abbreviated as SIA unit consists of three binary outputs. Figure 5-5 SIA unit 5.4.2 Installing the slotted initiator alarm unit Installing the SIA unit Proceed as follows to install the SIA unit: 1.
  • Page 65: Setting The Limits Of The Slotted Initiator Alarm Unit

    Installing the optional modules 5.4 Slotted initiator alarm unit 8. Place the insulating cover on the SIA unit by bending the container walls carefully. 9. Engage the motherboard into the four brackets. 10. Fix the motherboard using both the fixing screws. 11.
  • Page 66: Mechanical Limit Switch Module

    Installing the optional modules 5.5 Mechanical limit switch module Note The actuating discs are relatively difficult to move. This design prevents their unintentional movement during operation. You can achieve an easier and finer adjustment by reducing friction temporarily. Move the actuator to and fro while simultaneously holding the actuating discs.
  • Page 67 Installing the optional modules 5.5 Mechanical limit switch module The mechanical limit switch module consists of: ● One binary output to display a collective fault message. Compare with the device features of the alarm unit. ● Two switches to report two mechanically adjustable limits. Both these switches are electrically independent from the remaining electronic unit.
  • Page 68: Setting The Limits Of The Mechanical Limit Switch Module

    Installing the optional modules 5.6 EMC filter module 5.5.2 Setting the limits of the mechanical limit switch module Setting the L1 and L2 limits Proceed as follows to set the limits: 1. Move the actuator to the first desired mechanical position. 2.
  • Page 69 Installing the optional modules 5.6 EMC filter module Figure 5-7 EMC module Installation Proceed as follows to install the EMC filter module: 1. Remove the module cover. 2. Dismantle all existing optional modules. 3. Unlatch the fixing screws of the module rack that is opposite to the blanking plugs. 4.
  • Page 70: Accessories

    Installing the optional modules 5.7 Accessories Accessories Pressure gauge block Pressure gauge blocks that are available as accessories are illustrated below. The gauges display measured values for the actuating pressure and supply air. The image to the left shows the pressure gauge block for single-action actuators. The image to the right shows the pressure gauge block for dual-action actuators.
  • Page 71: Set Of Signs For The Non-Intrinsically Safe Version

    Installing the optional modules 5.8 Set of signs for the non-intrinsically safe version Set of signs for the non-intrinsically safe version Warning labels Fasten the included warning label on the side across from the type plate. There are different warning labels depending on the housing material, as described below. Figure 5-8 Warning label for a device with a plastic enclosure Figure 5-9...
  • Page 72 Installing the optional modules 5.8 Set of signs for the non-intrinsically safe version SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 73: Connect

    Connect Connect electrically 6.1.1 Note regarding electromagnetic compatibility Electromagnetic compatibility The plastic enclosure is metallized from inside to increase the electromagnetic compatibility (EMC) with respect to high-frequency radiation. The shield is connected to the threaded bush shown in the following picture such that it is electrically conductive. Note that this protection is effective only if you connect at least one of these bushes to the earthed control valves through electrically conductive (bare) attachments.
  • Page 74: Safety Notes For Electrical Connections

    Connect 6.1 Connect electrically 6.1.2 Safety notes for electrical connections WARNING Electrical connections in hazardous areas Regulations in the test certificate applicable for your country must be followed. National regulations and laws for hazardous areas applicable in your country must be followed for electrical connections.
  • Page 75: Interference Immunity

    Connect 6.1 Connect electrically Note Use in zones 2 and 22 In normal operation, non-arcing resources for zones 2 and 22 may not be connected or disconnected under voltage. However, the positioners can be connected and disconnected under voltage when installing or repairing;...
  • Page 76: Safety Shutdown

    Connect 6.1 Connect electrically 6.1.4 Safety shutdown The positioner is equipped with an additional input (terminal 81 [+] and terminal 82 [-]) to approach the safety position. After activating this function, this input must be continuously supplied with +24 V in order to retain the normal control function. If this auxiliary voltage fails or is switched, the exhaust air valve is forced-opened and the actuator moves to the defined safety position so that the actuator cannot be moved using the buttons on the device and the master.
  • Page 77 Connect 6.1 Connect electrically 2. Open the enclosure of the positioner by unlatching the four cover screws. 3. Insert the prepared bus cable through the cable inlet. 4. Fasten the shield using the clamp and both the screws on the enclosure. 5.
  • Page 78: Connections For "Non-Intrinsically Safe" Versions Or Versions With "Flameproof Enclosures

    Connect 6.1 Connect electrically 6. Connect the red and the green wires to terminals 3 and 7 of the motherboard as shown in the following picture. The polarity does not play any role here. Figure 6-4 Connecting the bus cable for versions with flameproof enclosures ①...
  • Page 79: Current Output

    Connect 6.1 Connect electrically Figure 6-6 Connecting the standard controller with flameproof enclosure 6.1.6.2 Current output ≤ 35 V module 6DR4004-8J Figure 6-7 module 6DR4004-8J, not Ex SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 80: Binary Inputs And Outputs

    Connect 6.1 Connect electrically 6.1.6.3 Binary inputs and outputs ≥ 1 Digital input 2 Fault message Limit value A1 Limit value A2 Figure 6-8 Alarm unit 6DR4004-8A, not Ex 6.1.6.4 SIA unit Figure 6-9 SIA unit 6DR4004-8G, not Ex SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 81: Mechanical Limit Switch Module

    Connect 6.1 Connect electrically 6.1.6.5 Mechanical limit switch module Safety note for low-voltage supply DANGER Low-voltage supply When you supply the module in the non-intrinsically safe version with low voltage, you must be sure to observe the following safety rules before starting work on the device: 1.
  • Page 82 Connect 6.1 Connect electrically NOTICE Installing/connecting Only qualified personnel is permitted to install and connect the mechanical limit switch module. NOTICE To observe before connecting Before you connect the mechanical limit switch module, observe the following conditions: • Only qualified personnel is permitted to connect the mechanical limit switch module. •...
  • Page 83 Connect 6.1 Connect electrically Mechanical limit switch module wiring diagram, not Ex Figure 6-10 Mechanical limit switch module 6DR4004-8K, not Ex Connecting the mechanical limit switch module Connect Connect the mechanical limit switch module as follows: 1. Loosen the screw ⑱ on the transparent cover ⑲. 2.
  • Page 84 Connect 6.1 Connect electrically Figure 6-11 Connecting the cables ⑱ Screw ⑲ Cover ⑳ Cable tie SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 85: Connection For The "Intrinsically Safe" Type Of Protection

    Connect 6.1 Connect electrically 6.1.7 Connection for the "intrinsically safe" type of protection 6.1.7.1 Standard controller WARNING Circuits Only the certified circuits may be connected as auxiliary power supply, control and signal circuits. Figure 6-12 Electrical connection for the intrinsically safe version of the standard controller SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 86: Current Output

    Connect 6.1 Connect electrically 6.1.7.2 Current output WARNING Circuits Only the certified circuits may be connected as auxiliary power supply, control and signal circuits. ≤ 30 V module 6DR4004-6J Intrinsically safe power source Figure 6-13 module 6DR4004-6J, EEx i SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 87: Binary Inputs And Outputs

    Connect 6.1 Connect electrically 6.1.7.3 Binary inputs and outputs WARNING Circuits Only the certified circuits may be connected as auxiliary power supply, control and signal circuits. Figure 6-14 Alarm unit 6DR4004-6A, EEx i SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 88: Sia Unit

    Connect 6.1 Connect electrically 6.1.7.4 SIA unit WARNING Circuits Only the certified circuits may be connected as auxiliary power supply, control and signal circuits. Figure 6-15 SIA unit 6DR4004-6G, EEx i 6.1.7.5 Mechanical limit switch module Safety notes for connecting the mechanical limit switch module WARNING Protection against mechanical influences In order to guarantee the degree of protection IP66/NEMA 4x, you must protect the module...
  • Page 89 Connect 6.1 Connect electrically NOTICE Maximal values for terminals 41/42 and 51/52 The following maximum values concern only terminals 41, 42, 51, and 52: • Maximum voltage: – Not Ex: AC 250 V or DC 24 V – Ex: 30 V DC •...
  • Page 90 Connect 6.1 Connect electrically Mechanical limit switch module wiring diagram, EEx i WARNING Electrical circuits Only certified intrinsically safe electrical circuits can be connected as power supply, control, and signal electrical circuits. Figure 6-16 Mechanical limit switch module 6DR4004-6K, EEx i Connecting the mechanical limit switch module Connect Connect the mechanical limit switch module as follows:...
  • Page 91 Connect 6.1 Connect electrically Figure 6-17 Connecting the cables ⑱ Screw ⑲ Cover ⑳ Cable tie SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 92: Connection For The "N" Type Of Protection

    Connect 6.1 Connect electrically 6.1.8 Connection for the "n" type of protection 6.1.8.1 Standard controller Figure 6-18 Connection of the standard controller version with the "n" type of protection 6.1.8.2 Current output Figure 6-19 module 6DR4004-6J, EEx n SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 93: Binary Inputs And Outputs

    Connect 6.1 Connect electrically 6.1.8.3 Binary inputs and outputs Binary inputs and outputs Figure 6-20 Alarm unit 6DR4004-6A, EEx n SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 94: Sia Unit

    Connect 6.1 Connect electrically 6.1.8.4 SIA unit SIA unit Figure 6-21 SIA unit 6DR4004-6G, EEx n SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 95: Pneumatic Connection

    Connect 6.2 Pneumatic connection Pneumatic connection WARNING Owing to safety reasons, the pneumatic auxiliary power supply must be fed after installation only if the positioner is switched to the "P-manual mode" when an electrical signal is available, refer to the as-delivered condition. NOTICE Observe the specifications regarding the air quality.
  • Page 96 Connect 6.2 Pneumatic connection SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 97: Operation

    Operation Operating elements 7.1.1 Digital display Introduction Note Repetition rate display When operated in temperature ranges below -10°C, the liquid crystal display of the positioner becomes sluggish and the repetition rate display reduces considerably. The digital display has two lines. These two lines are segmented differently. Each element in the upper line has 7 segments, whereas that in the lower line has 14 segments.
  • Page 98 Operation 7.1 Operating elements Operating mode Representation in the digital Pos. Legend display Configuration ① Parameter value ② Parameter name ③ Parameter number Manual mode (MAN) ① Position [%] ② Setpoint [%] ③ Fault message Automatic (AUT) ① Position [%] ②...
  • Page 99 Operation 7.1 Operating elements Figure 7-1 Digital display and buttons of the positioner ① Digital display ② Operating mode button ③ Decrement button ④ Increment button ● You can use three buttons to operate the positioner. ● The function of the buttons depends on the mode selected. ●...
  • Page 100: Firmware Version

    Operation 7.2 Operating modes 7.1.2 Firmware version The current firmware version is displayed when you exit the configuration menu. Figure 7-2 Firmware version, e.g. Version 4.00.00 Operating modes 7.2.1 Overview of operating modes You have five operating modes at your disposal to operate the positioner: 1.
  • Page 101: Changing The Operating Mode

    Operation 7.2 Operating modes 7.2.2 Changing the operating mode The following picture illustrates the available operating modes and switching between the operating modes. Figure 7-3 Switching between the operating modes See also Digital display (Page 97) SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 102: Overview Of Configuration

    Operation 7.2 Operating modes 7.2.3 Overview of configuration The following picture illustrates the handling of operating modes such as "Configuration" and "Initialization mode": Figure 7-4 Overview of the "Configuration" operating mode 7.2.4 Description of operating modes P-manual mode Note The "P-manual mode" is preset for the positioner in the as-delivered condition. The digital display of the positioner shows the current potentiometer position in the upper line.
  • Page 103 Operation 7.2 Operating modes Configuration and initialization You can access the "Configuration" mode by pressing the operating mode button for at least 5 seconds. You can use the "Configuration" mode to adjust the positioner individually as per your actuator and start commissioning or initialization. The positioner reports the "Configuration"...
  • Page 104: Optimizing The Controller Data

    Operation 7.3 Optimizing the controller data Diagnostics Proceed as follows to call the "Diagnostics" mode from the "Automatic" or "Manual" modes: 1. Press all three buttons of the positioner. 2. Keep these buttons pressed for more than 2 seconds. Current operating data can be called and displayed in this mode, e.g.: ●...
  • Page 105 Operation 7.3 Optimizing the controller data 22 lmpulse length up / 23 lmpulse length down You can use these parameters to determine the smallest impulse lengths for each actuating direction. The actuator is then moved with these lengths. The optimum value depends on the volume of the actuator in particular.
  • Page 106 Operation 7.3 Optimizing the controller data SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 107: Functional Safety

    Functional safety General safety notes 8.1.1 Safety-instrumented system Definition: Safety-instrumented system A safety-instrumented system executes the safety functions that are required to achieve or maintain a safe status in a system. It consists of a sensor, logic unit/control system and final controlling element.
  • Page 108 Functional safety 8.1 General safety notes Figure 8-1 Example of a safety-instrumented system (SIS) Function The transmitter generates a process-specific measured value. The programmable controls (SPS) monitors this value in case it exceeds a preset limit value. If a fault occurs, the SPS generates a shut-off signal for the connected positioner.
  • Page 109: Safety Integrity Level (Sil)

    Functional safety 8.1 General safety notes 8.1.2 Safety Integrity Level (SIL) Definition: SIL The international standard IEC 61508 defines four discrete Safety Integrity Levels (SIL) from SIL 1 to SIL 4. Each level corresponds to the probability range for the failure of a safety function.
  • Page 110: Device-Specific Safety Notes

    Functional safety 8.2 Device-specific safety notes HFT (for type A sub-systems) < 60% SIL 1 SIL 2 SIL 3 60 to 90% SIL 2 SIL 3 SIL 4 90 to 99% SIL 3 SIL 4 SIL 4 > 99% SIL 3 SIL 4 SIL 4 Device-specific safety notes...
  • Page 111: Settings

    Functional safety 8.2 Device-specific safety notes ● The electrical auxiliary power supply from the PROFIBUS PA or the FOUNDATION fieldbus connection fails ● Failure of auxiliary pneumatic power The safety function is not effected by other device functions, particularly the microcontroller, software and communication interface.
  • Page 112: Behavior In Case Of Faults

    The serial number can be found on the type plate. The address of the responsible repair center, contacts, spare parts lists, etc. can be found on the internet. See also Fault identification (Page 236) Services & Support (http://www.siemens.com/automation/service&support) Partner (http://www.automation.siemens.com/partner) SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 113: Maintenance/Checking

    Functional safety 8.2 Device-specific safety notes 8.2.5 Maintenance/Checking Checking the function We recommend that the functioning of the positioner is checked at regular intervals of one year. Checking safety You should regularly check the safety function of the entire safety circuit in line with IEC 61508/61511.
  • Page 114 Functional safety 8.2 Device-specific safety notes ● The connected valve actuator must be single acting and switch the valve to its safe end position by spring force in the following cases: – Pressure failure – At a chamber pressure (Y1 connection) up to a third of the maximum available inlet pressure (Pz connection) ●...
  • Page 115: Commissioning

    Commissioning Overview NOTICE • During the initialization process, the operating pressure must be at least one bar more than that required to close or open the valve. However, the operating pressure should not be greater than the maximum permissible operating pressure for the actuator. •...
  • Page 116: Sequence Of Automatic Initialization

    Commissioning 9.2 Sequence of automatic initialization ● Copying the initialization data when replacing a positioner: the initialization data of a positioner can be read and copied into another positioner. A defective device can thus be replaced without interrupting an ongoing process through initialization.
  • Page 117 Commissioning 9.2 Sequence of automatic initialization Sequence of RUN1 This structured chart describes the process to establish the direction of action. SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 118 Commissioning 9.2 Sequence of automatic initialization Sequence of RUN2 for part-turn actuators This structured chart describes the sequence for checking the actuator travel. It also contains the information about the sequence for trimming the zero point and the stroke. SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 119 Commissioning 9.2 Sequence of automatic initialization Sequence of RUN2 for linear actuators This structured chart describes the process to determine the actuator travel checks. It also contains the information about the sequence for trimming the zero point and the stroke. SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 120 Commissioning 9.2 Sequence of automatic initialization Sequence of RUN3 to RUN5 for part-turn and linear actuators This structured chart describes: ● Establishing and display of the actuating time/leak monitoring in RUN3 ● Minimization of controller increments in RUN4 ● Optimization of the transient response in RUN5 SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 121 Commissioning 9.2 Sequence of automatic initialization SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 122: Commissioning The Linear Actuators

    Commissioning 9.3 Commissioning the linear actuators Commissioning the linear actuators 9.3.1 Preparing linear actuators for commissioning Condition You have already installed the positioner using the suitable mounting kit. Setting the transmission ratio selector Note The setting of the transmission ratio selector is extremely important to commission the positioner.
  • Page 123: Automatic Initialization Of Linear Actuators

    Commissioning 9.3 Commissioning the linear actuators Setting the actuator 1. Check whether the mechanical unit can be moved freely in the entire actuating range. Move the actuator to the respective end position using the buttons. Press both the direction buttons simultaneously to reach the end position faster. 2.
  • Page 124 Commissioning 9.3 Commissioning the linear actuators 2. Call the second parameter "YAGL". Press the operating mode button for a short while for this purpose. The following is shown on the digital display depending on the setting: 3. Check whether the value displayed in the "YAGL" parameter matches the setting of the transmission ratio selector.
  • Page 125: Manual Initialization Of Linear Actuators

    Commissioning 9.3 Commissioning the linear actuators Setting parameter 3 Proceed as follows to set parameter 3: 1. On the scale of the lever, read the value marked by the carrier pin. 2. Set the parameter to the read value. Use the increment or decrement buttons for this purpose.
  • Page 126 Commissioning 9.3 Commissioning the linear actuators 2. Call the second parameter "YAGL". Press the operating mode button for a short while for this purpose. The following is shown on the digital display depending on the setting: 3. Check whether the value displayed in the "YAGL" parameter matches with the setting of the transmission ratio selector.
  • Page 127 Commissioning 9.3 Commissioning the linear actuators 8. Determine the end position 1 of the actuator spindle. Move the actuator spindle to the desired position by pressing the increment or decrement buttons. Accept the current position of the actuator spindle by pressing the operating mode button.
  • Page 128: Commissioning The Part-Turn Actuators

    Commissioning 9.4 Commissioning the part-turn actuators Aborting the manual initialization process 1. Press the operating mode button. The digital display shows the "INITM" parameter. The positioner is in the "Configuration" mode. 2. Exit the "Configuration" mode. Keep the operating modes button pressed for more than 5 s.
  • Page 129: Automatic Initialization Of Part-Turn Actuators

    Commissioning 9.4 Commissioning the part-turn actuators Note Press the increment or decrement buttons additionally to reach the end position faster. 3. After checking, move the actuator to a central position. This accelerates the initialization process. 9.4.2 Automatic initialization of part-turn actuators Condition The following conditions must be fulfilled before activating the automatic initialization: 1.
  • Page 130: Manual Initialization Of Part-Turn Actuators

    Commissioning 9.4 Commissioning the part-turn actuators 5. Start the initialization process. Keep the button pressed for more than 5 s until the following is shown on the digital display: Note The positioner runs through five initialization steps during the automatic initialization process.
  • Page 131 Commissioning 9.4 Commissioning the part-turn actuators 3. The displayed potentiometer position is within the permissible range between "P5.0" and "P95.0". NOTICE Setting of the adjustment angle The usual adjustment angle for part-turn actuators is 90°. Accordingly set the transmission ratio selector in the positioner to 90°. Initializing the positioner manually 1.
  • Page 132 Commissioning 9.4 Commissioning the part-turn actuators 7. Determine the end position 1 of the actuator. 8. Move the actuator spindle to the desired position by pressing the increment or decrement buttons. 9. Accept the current position by pressing the operating mode button. The following is shown on the digital display: Note RANGE fault message...
  • Page 133: Copying The Initialization Data When Replacing A Positioner

    Commissioning 9.5 Copying the initialization data when replacing a positioner Copying the initialization data when replacing a positioner ● Electropneumatic positioners can be replaced in a running system without interrupting the process. ● By copying and transferring the device and initialization data, it is possible to commission a replacement positioner without needing to initialize it.
  • Page 134 Commissioning 9.5 Copying the initialization data when replacing a positioner 7. Use the parameterization tool to transfer the saved device and initialization data to the replacement positioner. 8. If the displayed actual position value differs from the noted value, correct the deviation by moving the friction clutch.
  • Page 135: Parameter Assignment/Addressing

    Parameter assignment/Addressing 10.1 Overview of the parameters 10.1.1 Overview of parameters 1 to 5 Introduction Parameters 1 to 5 are the same for all versions of positioner. These parameters are used to adjust the positioner to the actuator. Normally the parameter setup is sufficient to be able to operate the positioner on an actuator.
  • Page 136: Overview Of Parameters 6 To 53

    Parameter assignment/Addressing 10.1 Overview of the parameters Parameter Function Parameter values Unit 3.YWAY Range of stroke (optional setting) 5 | 10 | 15 | 20 (Short lever 33°) 25 | 30 | 35 (Short lever 90°) 40 | 50 | 60 | 70 | 90 | 110 | 130 (Long lever 90°) 4.INITA Initialization (automatic)
  • Page 137 Parameter assignment/Addressing 10.1 Overview of the parameters Overview of the positioner parameters 6 to 53 Parameter Function Parameter values Unit 33 : 1 n1 - 33 50 : 1 n1 - 50 Freely adjustable FrEE 10.SL0 ... Setpoint turning points with free characteristic 30.SL20 10.SL0 0 ...
  • Page 138 Parameter assignment/Addressing 10.1 Overview of the parameters Overview of the positioner parameters 6 to 53 Parameter Function Parameter values Unit 40.AFCT Alarm function Normal Inverted none A1 = Min, A2 = Max A1 = Min, A2 = Min A1 = Max, A2 = Max 41.A1 Response threshold alarm 1 0.0 ...
  • Page 139: Overview Parameters A To P

    Parameter assignment/Addressing 10.1 Overview of the parameters Overview of the positioner parameters 6 to 53 Parameter Function Parameter values Unit 53.IDENT Device operating mode (ID No.) Independent of manufacturer Full functionality Setpoint turning points only appear when "9.SFCT = FrEE" is selected. Normally closed Operation when a switch is open or Low level contact means:...
  • Page 140 Parameter assignment/Addressing 10.1 Overview of the parameters Parameter Function Parameter values Unit A5.INTRV Test interval OFF / 1 ... 365 Days A6.PSTIN Partial stroke test reference step time NOINI / (C)##.# / Fdini / rEAL A7.FACT1 Factor 1 0.1 ... 1.5 ... 100.0 A8.FACT2 Factor 2 0.1 ...
  • Page 141 Parameter assignment/Addressing 10.1 Overview of the parameters Overview parameter F Parameter Function Parameter values Unit F. ZERO Zero point monitoring with the following parameters: F1.LEVEL1 Threshold 1 0.1 ... 1.0 ... 10.0 F2.LEVEL2 Threshold 2 0.1 ... 2.0 ... 10.0 F3.LEVEL3 Threshold 3 0.1 ...
  • Page 142: Description Of Parameters

    Parameter assignment/Addressing 10.2 Description of parameters Parameter Function Parameter values Unit L4.FACT3 Factor 3 0.1 ... 5.0... 40.0 Overview parameter O Parameter Function Parameter values Unit O. DCHG Monitoring the changes in direction with the following parameters: O1.LIMIT Limit for the number of changes of direction 1 ...
  • Page 143 Parameter assignment/Addressing 10.2 Description of parameters the factory such that it displays values between "P49.0" and "P51.0" when the lever on the feedback shaft is perpendicular to the linear actuator spindle. ● YFCT = LWAY Use this parameter value for: –...
  • Page 144: Description Of Parameters 3 To 5

    Parameter assignment/Addressing 10.2 Description of parameters The factory setting is "33°". 10.2.1.1 Description of parameters 3 to 5 3.YWAY - display of the range of stroke Use this parameter to set the value for the real range of stroke. This parameter is optional. You must set this parameter only if the determined value in mm is to be displayed at the end of the initialization process of a linear actuator.
  • Page 145: Description Of Parameters 6 To 53

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.2 Description of parameters 6 to 53 10.2.2.1 Description of parameter 6 6.SDIR - setpoint direction Use this parameter to set the setpoint direction. The setpoint direction is used to reverse the direction of action of the setpoint. The setpoint direction is mainly used for single-acting actuators with the "uP"...
  • Page 146: Description Of Parameters 10 To 30

    Parameter assignment/Addressing 10.2 Description of parameters Valve characteristic curve Setting with parameter value Inverse equal percentage 25:1 n1-25 Inverse equal percentage 33:1 n1-33 Inverse equal percentage 50:1 n1-50 Freely adjustable FrEE The factory setting is "Lin". See also Description of parameters 10 to 30 (Page 146) 10.2.2.4 Description of parameters 10 to 30 10.SL0 to 30.SL20 - setpoint support points...
  • Page 147: Description Of Parameter 31

    Parameter assignment/Addressing 10.2 Description of parameters Setpoint support points can be entered only for "9.SFCT = FrEE". You may only enter a monotonously rising characteristic curve, and two successive support values must differ by at least 0.2%. The factory setting is "0", "5" ... "95", "100". See also Description of parameter 9 (Page 145) 10.2.2.5...
  • Page 148: Description Of Parameter 34

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.2.7 Description of parameter 34 34.YNRM - standardization of manipulated variable Use the "YA" and "YE" parameters to restrict the manipulated variable. This restriction results in two different scales, MPOS and FLOW, for the digital display and the position feedback through the current output.
  • Page 149: Description Of Parameter 35

    Parameter assignment/Addressing 10.2 Description of parameters Figure 10-1 Dependency of the stroke on standardization and on "YA" and "YE" The factory setting is "MPOS". See also Description of parameters 32 and 33 (Page 147) Description of parameter 40 (Page 151) Description of parameters 41 and 42 (Page 153) 10.2.2.8 Description of parameter 35...
  • Page 150: Description Of Parameters 36 And 37

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.2.9 Description of parameters 36 and 37 36.YCDO - value "down tight closing" The factory setting is "0". 37.YCUP- value "up tight closing" Note "36.YCDO" must always be set greater than "37.YCUP". The tight closing function has a fixed hysteresis of 1%.
  • Page 151: Description Of Parameter 40

    Parameter assignment/Addressing 10.2 Description of parameters If the binary input is activated, the actuator uses the value defined by "YA" and "YE" for controlling in the "Automatic" mode. ● BIN1 or BIN2 (contact closed) = StoP or -StoP (contact open). In "Automatic"...
  • Page 152 Parameter assignment/Addressing 10.2 Description of parameters Direction of action and hysteresis A1 = 52 AFCT = MIN / MAX A2 = 48 Path = 45 Active Path = 50 Active Active Path = 55 Active A1 = 52 AFCT = -MIN / -MAX A2 = 48 Path = 45 Active...
  • Page 153: Description Of Parameters 41 And 42

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.2.12 Description of parameters 41 and 42 41.A1 - response threshold of alarm 1 The factory setting is "10.0". 42.A2 - response threshold of alarm 2 Use these parameters to set the alarm thresholds that are used to trigger an alarm. The response thresholds of the "41.A1"...
  • Page 154: Description Of Parameter 44

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.2.14 Description of parameter 44 44.TIM - monitoring time to set the fault messages Use this parameter to set the value in seconds before which the positioner must attain the corrected status. The corresponding response threshold is defined using the "45. LIM" parameter.
  • Page 155: Description Of Parameter 46

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.2.16 Description of parameter 46 46. STRK - limit for monitoring the path integral (number of strokes) Use this parameter to set the limit for the path integral. This parameter corresponds to the profile parameter "TOTAL_VALVE_TRAVEL_LIMIT". NOTICE Limit overshoot A fault message is not triggered if the set limit is exceeded.
  • Page 156: Description Of Parameter 48

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.2.18 Description of parameter 48 48.XDIAG - activation of advanced diagnostics Advanced diagnostics is deactivated by default. The "48.XDIAG" parameter is thus set to "OFF". Three operating modes are available to activate advanced diagnostics: ●...
  • Page 157: Description Of Parameter 49

    Parameter assignment/Addressing 10.2 Description of parameters Figure 10-4 Display of a threshold 3 fault message The factory setting is "OFF". See also Description of parameter A (Page 159) XDIAG parameter (Page 231) 10.2.2.19 Description of parameter 49 49.FSTY - safety position Use this parameter to move the actuator to a defined safety position when communication fails.
  • Page 158: Description Of Parameter 51

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.2.21 Description of parameter 51 51.FSVL - safety setpoint Default value of the safety position. Note that the "FSVL" safety setpoint of 0% always refers to the mechanical position in which the actuator is depressurized. The mechanical position is especially important if you have set the "6.SDIR"...
  • Page 159: Description Of Parameters A To P

    Parameter assignment/Addressing 10.2 Description of parameters A blinking decimal point in the upper line of the positioner display indicates communication with an acyclic master. The factory setting is "1". See also Cyclic data transfer (Page 192) 10.2.3 Description of parameters A to P 10.2.3.1 Description of parameter A A.
  • Page 160 Parameter assignment/Addressing 10.2 Description of parameters A3.STEP - step height Use this sub-parameter to define the step height of the partial stroke test in percent. Set the step height in a range from "0.1" to "100.0". The factory setting is "10.0". A4.STEPD - step direction Use this sub-parameter to set the step direction of the partial stroke test.
  • Page 161 Parameter assignment/Addressing 10.2 Description of parameters Example: An average actuating time of 1.2 seconds is shown in the digital display as "C 1.2", where "C" stands for "calculated". The average actuating time can be used as a reference step time. However, it merely represents a rough standard value. Set the sub-parameters "A1"...
  • Page 162: Description Of Parameter B

    Parameter assignment/Addressing 10.2 Description of parameters See also Description of parameter 48 (Page 156) 10.2.3.2 Description of parameter b b. DEVI - general control valve fault Use this parameter to activate the general control valve fault test for dynamic monitoring of the control valve response.
  • Page 163: Description Of Parameter C

    Parameter assignment/Addressing 10.2 Description of parameters The threshold 1 fault message is displayed when the limit threshold 1 is exceeded. The process to activate and display this fault message is described in the "XDIAG" parameter. The factory setting is "5.0". b4.FACT2 - factor 2 Use this sub-parameter to set the factor for the formation of limit threshold 2.
  • Page 164 Parameter assignment/Addressing 10.2 Description of parameters C1.LIMIT - limit of the leakage indicator Use this sub-parameter to set the limit of the leakage indicator in percent. Set the limit in a range from "0.1" to "100.0". There is no leakage if the limit is less than "30.0". Utilize the complete sensitivity of the leakage detection as follows: 1.
  • Page 165: Description Of Parameter D

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.3.4 Description of parameter d d. STIC - static friction/slipstick effect Use this parameter to continuously monitor the current static friction of the final controlling element (slipstick). If the parameter is activated, the positioner detects the slipstick effects that may occur.
  • Page 166: Description Of Parameter E

    Parameter assignment/Addressing 10.2 Description of parameters d4.FACT3 - factor 3 Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in a range from "0.1" to "100.0". The limit threshold is the product of "d1.LIMIT" and "d4.FACT3".
  • Page 167: Description Of Parameter F

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.3.6 Description of parameter F F. ZERO - zero point displacement Note Fault detection The monitoring unit for the zero point displacement responds to the fault in the valve. If the limit thresholds of the zero point displacement are exceeded due to misalignment of the position feedback, the misalignment also triggers a diagnostics message.
  • Page 168: Description Of Parameter G

    Parameter assignment/Addressing 10.2 Description of parameters The positioner triggers a fault message if the difference between the lower hard end stop and the initialization value undershoots threshold 2. The process to activate and display this fault message is described in the "XDIAG" parameter. The factory setting is "2.0".
  • Page 169: Description Of Parameter H

    Parameter assignment/Addressing 10.2 Description of parameters The factory setting is "OFF". G1.LEVL1 - threshold 1 Use this sub-parameter to set a threshold in percent. Use threshold 1 to monitor the upper hard end stop. Set the threshold in a range from "0.1" to "10.0". The positioner triggers a fault message if the difference between the upper hard end stop and the initialization value exceeds threshold 1.
  • Page 170: Description Of Parameter J

    Parameter assignment/Addressing 10.2 Description of parameters H1.TUNIT - temperature unit Use this sub-parameter to set the temperature unit "°C" or "°F". The selected temperature unit is then also applicable for all other temperature-based parameters. The factory setting is "°C". H2.LEVL1 - threshold 1 Use this sub-parameter to set a threshold in "°C"...
  • Page 171 Parameter assignment/Addressing 10.2 Description of parameters 2. Set the suitable parameter values in sub-parameters. The setting options available in sub-parameters are described below. The positioner generates a fault message if the upper limit temperature exceeds a threshold during the test. The factory setting is "OFF".
  • Page 172: 10.2.3.10 Description Of Parameter L

    Parameter assignment/Addressing 10.2 Description of parameters 10.2.3.10 Description of parameter L L. STRK - monitoring the path integral Use this parameter to monitor the entire path covered by the final controlling element continuously. Configure the following settings to activate the test: 1.
  • Page 173: 10.2.3.11 Description Of Parameter O

    Parameter assignment/Addressing 10.2 Description of parameters L4.FACT3 - factor 3 Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in a range from "0.1" to "40.0". The limit threshold is the product of "L1.LIMIT" and "L4.FACT3". The threshold 3 fault message is displayed when the limit threshold 3 exceeds.
  • Page 174: 10.2.3.12 Description Of Parameter P

    Parameter assignment/Addressing 10.2 Description of parameters The factory setting is "2.0". O4.FACT3 - factor 3 Use this sub-parameter to set the factor for the formation of limit threshold 3. Set the factor in a range from "0.1" to "40.0". The limit threshold is the product of "O1.LIMIT" and "O4.FACT3".
  • Page 175 Parameter assignment/Addressing 10.2 Description of parameters P2.STATE - status of the position average calculation Use this sub-parameter to start the calculation of the position average. If a reference average has never been determined yet, the parameter value is "IdLE". Then start the calculation by pressing the increment button for five seconds.
  • Page 176 Parameter assignment/Addressing 10.2 Description of parameters SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 177: Functions/Operations Using Profibus Pa

    Functions/operations using PROFIBUS PA 11.1 System integration A control system (master) uses acyclic and cyclic data transfer to operate and monitor the positioner. You must set an address of the positioner in advance so that it can communicate with the master as a slave. The PROFIBUS address is set to 126 in the as-delivered condition.
  • Page 178: Device" Menu

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer Procedure for acyclic data transfer: We recommend the following general procedure: 1. First read the current settings from the device using the "Load into PG/PC" menu item. 2. Check the current settings. 3.
  • Page 179: Update Diagnostics Status

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer 11.2.2.4 Update diagnostics status Use this sub-menu to update the diagnostics status in SIMATIC PDM that is visualized using symbols. Symbols are shown before the device name. The following table contains the symbols and the corresponding diagnostics status represented by these symbols: Meaning Symbols...
  • Page 180 Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer The above target modes are effective when the positioner is in the automatic mode (AUT). If the positioner is in the manual mode (MAN), they are effective only after an on-site switchover to the automatic mode (AUT). These target modes are saved in the positioner in the power failure-safe manner.
  • Page 181: Simulation

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer Note You must set the target mode to "Automatic" to reactivate the setpoints of the cyclic master. Out of service (O/S) You can use SIMATIC PDM to put the positioner out of service irrespective of the cyclic communication.
  • Page 182: Partial Stroke Test (Pst)

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer Simulation of actual value You can activate the actual value simulation in this tab and also define the actual value to be simulated and its quality and status. The following feedback values are available: ●...
  • Page 183: Pst Trace Characteristic

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer Functions Use the Partial stroke test button to access the functions of the partial stroke test: ● Start the partial stroke test. ● Stop the partial stroke test. ● Initialize the partial stroke test. Changes become effective as soon as the Transfer button is pressed.
  • Page 184: 11.2.2.11 Initialization Parameters

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer ● Static friction/slipstick ● Dead zone monitoring ● Lower end stop ● Upper end stop ● Lower limit temperature ● Upper limit temperature ● Path integral/number of strokes ● Change of direction ●...
  • Page 185: 11.2.2.13 Reset Pdm Parameters

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer Proceed as follows to initialize the positioner using SIMATIC PDM for the first time: 1. For this purpose, go to the "Device" menu and then to the "Initialization" sub-menu. A window containing an overview of initialization-relevant device parameters, checkback, device status, diagnostics and initialization status then opens.
  • Page 186: 11.2.2.15 Write Lock

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer If you remove a positioner from the PROFIBUS path, you must reset its address to 126 using this function, so that you can re-integrate a positioner in this or another system depending on the requirement.
  • Page 187: View" Menu

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer 11.2.3 "View" menu 11.2.3.1 Measured value display "Measured value" tab This tab contains: ● Bar graph displays of actual value and setpoint. ● Further information about the quality of values. ● Information about the valve position. ●...
  • Page 188: Device Status

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer 11.2.3.3 Device status Available tabs In this online menu, information about the device status is processed in the following four tabs: ● General ● Profile ● Status/Messages ● Device diagnostics "General" tab The "General"...
  • Page 189: Maintenance Information

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer 11.2.3.4 Maintenance information Available tabs The maintenance information is processed in the following six tabs: ● "Current maintenance information" tab ● "Maintenance information (last maintenance)" tab ● "Maintenance counter" tab ● "Operating temperature" tab ●...
  • Page 190: Trend Characteristic

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer 11.2.3.5 Trend characteristic Versions Use this menu item to access the following trend characteristics: ● Actual value ● Control deviation ● Leakage ● Static friction ● Lower end stop ● Upper end stop ●...
  • Page 191: Adjusting The View Of Simatic Pdm

    Functions/operations using PROFIBUS PA 11.2 Acyclic data transfer 11.2.3.7 Adjusting the view of SIMATIC PDM Function bar With this you can show or hide the function bar containing the color icons in the top margin of SIMATIC PDM. Status bar With this you can show or hide the status bar in the lower margin of SIMATIC PDM.
  • Page 192: Cyclic Data Transfer

    The useful data to be transferred in the cyclic operation is determined during the projecting planning. The data volume to be transferred can thus be optimized. The GSD files of all common devices are already stored in the Siemens control systems. GSD files can be imported later. You can download the GSD files from: www.siemens.de/sipartps2...
  • Page 193 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Figure 11-3 Example of a small PROFIBUS DP/PA system ① PC or PG (master class 2) ⑦ PA devices ② Power supply ⑧ DP/PA coupler/link ③ PROFIBUS DP ⑨ CPU SIMATIC S7 (master class 1) ④...
  • Page 194 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Figure 11-4 STEP 7 sample program In this example, all data in the input and output directions supported by the device are transferred. The selected peripheral starting address is 256 (W#16#100). Note Only the older SIMATIC CPUs require the SFC14 and SFC16 modules for consistent reading and writing.
  • Page 195: Useful Data Through Profibus

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer 11.3.3 Useful data through PROFIBUS Cyclic useful data The positioner can exchange a combination of the following cyclic useful data through PROFIBUS: Name Abbreviation Direction from the Length in Comprising: positioner's point of byte German English...
  • Page 196 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Meaning of "1" Remarks Emergency operation active The device is in the manual mode. Representation in the digital display: MAN or P Deviation of the movement direction Not required for the positioner. End stop reached (valve completely open) Not required for the positioner.
  • Page 197: Possible Combinations Of The Useful Data

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer 11.3.3.1 Possible combinations of the useful data Useful data and position in the address room You can select a combination of values for the communication of cyclic useful data between the master and the positioner: Setpoint: Output (master view) Starting address...
  • Page 198 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer READBACK, POS_D, SP Actual value, discrete position, setpoint: Input (master view) Starting address READBACK - floating point number READBACK - status POS_D POS_D - status Output (master view) Starting address SP - floating point number SP - status Checkback, SP Checkback, setpoint:...
  • Page 199 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer READBACK, CHECKBACK, POS_D, SP Actual value, discrete position, checkback, setpoint: Input (master view) Starting address READBACK - floating point number READBACK - status POS_D POS_D - status CHECKBACK Output (master view) Starting address SP - floating point number SP - status RCAS_OUT, CHECKBACK, RCAS_IN...
  • Page 200 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer READBACK, RCAS_OUT, POS_D, CHECKBACK, SP, RCAS_IN Actual value, remote cascade output, discrete position, checkback, setpoint, remote cascade input: Input (master view) Starting address READBACK - floating point number READBACK - status RCAS_OUT - floating point number RCAS_OUT - status POS_D POS_D - status...
  • Page 201: Diagnostics

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer 11.3.3.2 Diagnostics Function The positioner can report active information about its device status. These diagnoses are important information that can be used by an automation system to initiate remedial measures. Standard mechanisms of PROFIBUS-DP are used to transfer the diagnostics information and report it actively to the class 1 master.
  • Page 202: Adjustable Status (Condensed Status)

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer 11.3.4 Adjustable status (condensed status) Diagnostics messages are generated in the DIAGNOSTICS physical block parameter depending on the diagnostics events in the device. At the same time, the statuses of three PowerTags (FEEDBACK_VALUE, READBACK and POS_D) that are sent to the master by the SIPART PS2 PA positioner are affected.
  • Page 203 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Figure 11-6 Activating the condensed status for the device parameterization - with an example of HW configuration with SIMATIC S7 SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 204 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Figure 11-7 Activating the condensed status for the device parameterization - with an example of SIMATIC PDM SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 205: Diagnostics Messages In Case Of Deactivated Condensed Status

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer 11.3.4.1 Diagnostics messages in case of deactivated condensed status The diagnostics messages of the DIAGNOSTICS physical block parameter in case of the deactivated condensed status are shown in the following table: Byte Name and meaning Cause Measure...
  • Page 206: Diagnostics Messages In Case Of Activated Condensed Status

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Byte Name and meaning Cause Measure DIA_CHARACT The parameterized characteristic Modify the configuration data Characteristic curve invalid curve does not have the required (change the GSD) such that it is monotony, number of support consistent with the identification points, or the x values are not number set in the device.
  • Page 207 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Process-dependant: PROCESS RELATED Functional check: FUNCTION CHECK Collective diagnostics messages Collective diagnostics messages in the case of the activated condensed status are shown in the following table: Byte Name and meaning Cause Measure Group Reserved...
  • Page 208 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Byte Name and meaning Cause Measure Group IDENT_NUMBER_VIOLATION To determine the cause, check Modify the Identification number changed in DIAGNOSTICS_EXTENSION configuration data (change the GSD) DIAGNOSTICS_EXTENSION_2 such that it is which diagnostics event has consistent with the triggered the message.
  • Page 209: Definition Of The Status

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer 11.3.4.3 Definition of the status Status byte The status is used to provide information about the quality of the input and output values. This information is classified into four stages. Quality stages such as "Bad", "Uncertain", "Good"...
  • Page 210: Sub-Status For Activated Condensed Status

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Name profile German name Good, maintenance required Gut, Instandhaltungsbedarf Good (Cascade), ok Gut (Kaskade), Ok Good (Cascade), initialisation Gut (Kaskade), Initialisierung bestätigt acknowledged Good (Cascade), initialisation request Gut (Kaskade), Initialisierung angefordert Good (Cascade), not invited Gut (Kaskade), Nicht eingeladen Good (Cascade), local override Gut (Kaskade), Vor-Ort-Bedienung...
  • Page 211: List Of Diagnostics Events With Status And Diagnostics Message For Deactivated Condensed Status

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer 11.3.4.6 List of diagnostics events with status and diagnostics message for deactivated condensed status A list of diagnostics events with status and diagnostics message for deactivated condensed status is given in the following table. DIAGNOSTICS_EXTENSION and DIAGNOSTICS_EXTENSION_2 are physical block parameters.
  • Page 212 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer DIAGNOSTICS_EXTENSION_2 physical block parameter Byte Diagnostics events Hard-coded effect of a diagnostics event Quality status code DIAGNOSTICS bit General control valve fault Good, maintenance required DIA_MAINTENANCE (limit 1) General control valve fault Good, maintenance required DIA_MAINTENANCE (limit 2)
  • Page 213: List Of Diagnostics Events With Status And Diagnostics Message For Activated Condensed Status

    Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Hard-coded effect of a diagnostics event PST reference time exceeded Good, maintenance required DIA_MAINTENANCE (limit 2) PST reference time exceeded Good, maintenance required DIA_MAINTENANCE (limit 3) 76 ... 80 Reserved Permissible device Good, maintenance required DIA_TEMP_ELECTR temperature exceeded (limit 1)
  • Page 214 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Effect of the event Binary 2 is active (only Good, Ok DIA_MAINTENANCE_DEMAND M, F, P message) Action triggered by Good, Ok DIA_FUNCTION_CHECK M, F, P binary input 2 7 ... 21 Reserved Limit for alarm A1 Good, maintenance DIA_MAINTENANCE...
  • Page 215 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer DIAGNOSTICS_EXTENSION_2 physical block parameter Diagnostics events Effect of the event Quality status code DIAGNOSTICS bit Group General control valve Good, maintenance DIA_MAINTENANCE fault (limit 1) requirement General control valve Good, maintenance DIA_MAINTENANCE_DEMAND fault (limit 2) requirement General control valve...
  • Page 216 Functions/operations using PROFIBUS PA 11.3 Cyclic data transfer Effect of the event Limit 1 for position Good, maintenance DIA_MAINTENANCE M1, P average exceeded requirement Limit 2 for position Good, maintenance DIA_MAINTENANCE_DEMAND M12, P average exceeded demand Limit 3 for position Uncertain, maintenance DIA_MAINTENANCE_ALARM M, P...
  • Page 217: Alarm, Fault And System Messages

    Alarm, fault and system messages 12.1 Representation of system messages on the digital display 12.1.1 System messages before initialization Remarks about the tables: stands for variable numeric values Error symbol (Slash): texts to the left and the right of the slash blink alternately Messages before initialization (first commissioning) Message Line...
  • Page 218: System Messages During Initialization

    Alarm, fault and system messages 12.1 Representation of system messages on the digital display 12.1.2 System messages during initialization Remarks about the tables: stands for variable numeric values Error symbol (Slash): texts to the left and the right of the slash blink alternately Messages during initialization Message Line...
  • Page 219 Alarm, fault and system messages 12.1 Representation of system messages on the digital display Line Acknowledge with the operating mode The permissible measuring range of end • button; the remaining steps ("RUN1" to positions is achieved only in case of a "FINSH") execute automatically manual initialization Provide adequate compressed air...
  • Page 220: System Messages When Exiting The Configuration Mode

    Alarm, fault and system messages 12.1 Representation of system messages on the digital display Line Rectify the leakage if the value is too Value and unit of the result after the leakage • nn.n large test %/MIN Continue with the "+" button •...
  • Page 221: System Messages During Operation

    Alarm, fault and system messages 12.1 Representation of system messages on the digital display 12.1.4 System messages during operation Remarks about the tables: stands for variable numeric values Error symbol (Slash): texts to the left and the right of the slash blink alternately Messages during operation: Message Line...
  • Page 222 Alarm, fault and system messages 12.1 Representation of system messages on the digital display Line Operating mode Switch to the MAnn Manual mode • automatic mode (nn = setpoint) using the operating mode button Set the target LO nn Positioner is in the "local •...
  • Page 223: Diagnostics

    Alarm, fault and system messages 12.2 Diagnostics 12.2 Diagnostics 12.2.1 Display of diagnostics values You can access the diagnostics display from the automatic or manual mode by pressing all three buttons simultaneously for at least two seconds. The following table provides an overview of values that can be displayed. The third column contains the German meaning and the corresponding English term used to derive the abbreviation if it is not self-explanatory.
  • Page 224 Alarm, fault and system messages 12.2 Diagnostics Abbreviation Meaning Values that can Unit Reset be displayed possibl LEAK Leakage (Leakage) P 0.0 ... 100.0 Monitoring of the partial stroke test OFF / ###.#, fdini, s for ###.# notSt, SdtSt, fdtSt, notd, Strt PRPST Time since the last Partial-Stroke-Test ###, notSt, Sdtst,...
  • Page 225: Meaning Of Diagnostics Values

    Alarm, fault and system messages 12.2 Diagnostics Abbreviation Meaning Values that can Unit Reset be displayed possibl WT05 Number of operating hours in the actuating range 0 ... 4.29E9 Hours WT05 WT10 Number of operating hours in the actuating range 0 ...
  • Page 226 Alarm, fault and system messages 12.2 Diagnostics 5 A2CNT - number of alarms 2 The response of alarms 1 and 2 is counted using these two counters. Activation of alarms using the "AFCT" parameter is a condition for this. The counters can be set to zero using the increment button.
  • Page 227 Alarm, fault and system messages 12.2 Diagnostics ● FdtSt - Failed Test The last partial stroke test has failed. The following status messages appear when the larger button is pressed: ● notoL - No Tolerance The control valve is beyond the tolerance range to start the partial stroke test. A manual partial stroke test is not started.
  • Page 228 Alarm, fault and system messages 12.2 Diagnostics 17 ZERO - zero point displacement Display of the current displacement of the lower hard end stop with respect to its initialization value. The activation of the "down tight closing function" is a condition to determine this. Activate using the "YCLS"...
  • Page 229 Alarm, fault and system messages 12.2 Diagnostics 24 DBUP - dead zone up 25 DBDN - dead zone down The dead zones of the closed-loop controller in the "Up" and "Down" directions are displayed here. The values correspond to either the manually set value of the "DEBA" parameter or the automatically adapted value by the device if DEBA"...
  • Page 230 Alarm, fault and system messages 12.2 Diagnostics Operating hours in temperature ranges T1 to T2 40 VENT1 - number of switching cycles of pilot valve 1 41 VENT2 - number of switching cycles of pilot valve 2 Both these counters sum up the control processes of pilot valves and are used to assess the switching frequency.
  • Page 231: Online Diagnostics

    Alarm, fault and system messages 12.3 Online diagnostics Note All diagnostics values are updated in the non-volatile memory every 15 minutes so that, in case of a power failure, only the values of the previous 15 minutes may be lost. See also Safety function (Page 110) 12.3...
  • Page 232: Overview Of Error Codes

    Alarm, fault and system messages 12.3 Online diagnostics 12.3.3 Overview of error codes Overview of error codes that activate the fault message output Error Three- Event Parameter setting Fault message disappears Possible causes code stage when Remaining control Always active ...
  • Page 233: Meaning Of Error Codes

    Alarm, fault and system messages 12.3 Online diagnostics Error Three- Event Parameter setting Fault message disappears Possible causes code stage when Temperature H. TMIN≠OFF ... the lower temperature Ambient temperature too low undershot thresholds are no longer undershot. Temperature J. TMAX≠OFF ...
  • Page 234 Alarm, fault and system messages 12.3 Online diagnostics 4 Monitoring of the stroke number 5 Monitoring of the number of changes of direction Both the values, namely the stroke number and the number of changes of direction are constantly compared with the thresholds that are determined from the parameters "L1.LIMIT" to "L4.FACT3"...
  • Page 235 Alarm, fault and system messages 12.3 Online diagnostics stroke test that are determined from the "A6.PSTIN" reference step time multiplied by factors "A7.FACT1" to "A9.FACT3" is violated. The degree of the fault message is shown in the number of columns on the digital display. The degree of the fault message is simultaneously displayed using the fault message output or alarm outputs depending on the mode of the advanced diagnostics.
  • Page 236: Fault Correction

    Alarm, fault and system messages 12.4 Fault correction 12.4 Fault correction 12.4.1 Fault identification Diagnostics guide Fault See fault table In which mode does a fault occur? Initialization • Manual and automatic modes • In which environment and under which boundary conditions does a fault occur? Wet environment (e.g.
  • Page 237: Remedial Measures Table 2

    Alarm, fault and system messages 12.4 Fault correction Fault profile (symptoms) Possible cause(s) Remedial measures Positioner remains in "RUN 3". Actuator actuating time is too high. Open the restrictor completely • • • and/or set the pressure PZ (1) to the highest permissible value.
  • Page 238: Remedial Measures Table 3

    Alarm, fault and system messages 12.4 Fault correction 12.4.4 Remedial measures table 3 Fault profile (symptoms) Possible cause Remedial measures Actuator does not move. Compressed air < 1.4 bar Set the supply air pressure to • • • > 1.4 bar. Piezo valve does not activate (a Restrictor valve turned off (screw at Open the restrictor screw by turning...
  • Page 239: Remedial Measures Table 5

    Alarm, fault and system messages 12.4 Fault correction 12.4.6 Remedial measures table 5 Fault profile (symptoms) Possible cause(s) Remedial measures Zero point displaces sporadically Impact or shock loads result in Rectify the causes for shock loads. • • • (> 3%). accelerations so high that the Re-initialize the positioner.
  • Page 240 Alarm, fault and system messages 12.4 Fault correction SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 241: Service And Maintenance

    Service and maintenance 13.1 Service and maintenance The positioner is maintenance-free to a large extent. Screens are installed in the pneumatic connections of the positioners to protect them from rough dirt particles. If there are dirt particles in the pneumatic auxiliary power supply, they damage the screens and hamper the function of the positioner.
  • Page 242: Positioner In The Plastic Enclosure

    Service and maintenance 13.3 Positioner in the plastic enclosure 13.3 Positioner in the plastic enclosure DANGER Risk of explosion due to electrostatic charge Electrostatic charges develop when cleaning the positioner in the plastic enclosure with a dry cloth. It is imperative you avoid electrostatic charges in the hazardous environment. Dismantling 1.
  • Page 243: Technical Data

    Technical data 14.1 General technical data SIPART PS2 (all versions) General data Range of stroke (linear actuator) 3 ... 130 mm (0.12 ... 5.12") (angle of rotation of the feedback shaft 16 ... 90°) Angle of rotation (part-turn actuator) 30 ... 100° Installation On the linear actuator •...
  • Page 244 Technical data 14.1 General technical data General data mounting position Any; in wet environment, pneumatic connections and outlet opening not upward CE symbol Conformity in regards to EMC guideline 89/336 EEC in agreement with the following norms EMC requirements EN 61326/A1 App. A.1 and NAMUR NE21 August 98 Material Enclosure •...
  • Page 245 Technical data 14.1 General technical data Certificates and approvals Classification according to pressure equipment For fluid group 1 gases; fulfills requirements in directive (PED 97/23/EC) article 3, paragraph 3 (good engineering practice SEP) Pneumatic data Auxiliary power (air supply) Pressure •...
  • Page 246: Technical Data Of Sipart Ps2 Pa

    Technical data 14.2 Technical data of SIPART PS2 PA 14.2 Technical data of SIPART PS2 PA Standard controller Standard controller Standard controller Standard controller without explosion with EEx d explosion with EEx ia/ib with EEx n protection protection explosion protection explosion protection (flameproof enclosure)
  • Page 247 Technical data 14.2 Technical data of SIPART PS2 PA Electrical data Standard controller Standard controller Standard controller Standard controller without explosion with EEx d explosion with EEx ia/ib with EEx n explosion protection protection explosion protection protection (flameproof enclosure) Fault current 0 mA 0 mA 0 mA...
  • Page 248 Technical data 14.2 Technical data of SIPART PS2 PA Communication Standard controller Standard controller Standard controller Standard controller without explosion with EEx d explosion with EEx ia/ib with EEx n explosion protection protection explosion protection protection (flameproof enclosure) Layers 1 + 2 as per PROFIBUS PA, transmission technique as per IEC 1158-2; slave function layer 7 (protocol layer) as per PROFIBUS DP, standard EN 50170 with the extended PROFIBUS functionality (all data is acyclic, manipulated variables, feedbacks and statuses are additionally cyclic)
  • Page 249: Technical Data Of Optional Modules

    Technical data 14.3 Technical data of optional modules 14.3 Technical data of optional modules Optional modules Without explosion With EEx ia/ib explosion With EEx n explosion protection protection protection (also EEx d) Explosion protection as per II 2G EEx ia/ib II C II 3G EEx nA L [L] II C T6 EN 50014 and EN 50020 and T4/T5/T6...
  • Page 250 Technical data 14.3 Technical data of optional modules Alarm unit Without explosion With EEx ia/ib explosion With EEx n explosion protection protection protection (also EEx d) Galvanically connected with the • standard controller Signal status 0 Dry contact, open Dry contact, open Dry contact, open Signal status 1 Dry contact, closed...
  • Page 251 Technical data 14.3 Technical data of optional modules Mechanical limit switch module (not for Without explosion protection With EEx ia/ib explosion protection EEx d version) 6DR4004-8K 6DR4004-6K Limit indicator with mechanical switch contacts and fault message output Explosion protection Without II 2 G EEx ia/ib IIC T6 Max switching current AC/DC Connection to intrinsically safe...
  • Page 252 Technical data 14.3 Technical data of optional modules Non-contacting position sensor (not Without explosion With EEx ia/ib explosion With EEx n explosion for EEx d version) protection (also EEx d) protection protection Actuating range Linear actuator • 3 ... 130 mm (0.12 ... 3 ...
  • Page 253: Dimension Drawings

    Dimension drawings 15.1 Dimension drawings Positioner with plastic enclosure 6DR5xx0 Ø8 0.276 38,5 1.516 88,5 3.484 Figure 15-1 Dimensions of the plastic enclosure 6DR5xx0 version SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 254 Dimension drawings 15.1 Dimension drawings Terminal strip for positioner with plastic enclosure Figure 15-2 Dimensions of terminal strip and plastic enclosure SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 255 Dimension drawings 15.1 Dimension drawings Positioner with metal enclosure 6DR5xx1 Figure 15-3 Dimensions of the metal enclosure 6DR5xx1 version SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 256 Dimension drawings 15.1 Dimension drawings Positioner with flameproof metal enclosure 6DR5xx1 Figure 15-4 Dimensions of the positioner with the flameproof metal enclosure 6DR5xx5 SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 257: Scope Of Delivery/Spare Parts/Accessories

    Scope of delivery/spare parts/accessories 16.1 Overview WARNING Assembling the components When assembling components, ensure that only those positioners and optional modules are combined with each other that are approved for the corresponding operating range. This condition is particularly applicable for the safe operation of the positioner in the areas where the atmosphere may be potentially explosive (zones 1 and 2).
  • Page 258 Scope of delivery/spare parts/accessories 16.1 Overview Options The positioner can be equipped with different optional modules. The following modules are normally available: ● I module: two-wire current output 4 to 20 mA for position feedback ● Alarm unit: 3 binary outputs and 1 binary input ●...
  • Page 259: Standard Controller

    Scope of delivery/spare parts/accessories 16.2 Standard controller 16.2 Standard controller The following table shows the type range of different standard controllers: Standard controller Equipment 6DR5 Electronics Δ Δ Δ Δ Δ PS2 2L: 2 wire, without HART PS2 2L: 2 wire, with HART PS2 4L: 2, 3, 4 wire, without HART PS2 4L: 2, 3, 4 wire, with HART PS2 wire PROFIBUS PA...
  • Page 260: Optional Modules

    Scope of delivery/spare parts/accessories 16.3 Optional modules 16.3 Optional modules Option Order number module without explosion protection 6DR4004-8J module with PTB explosion protection 6DR4004-6J module with FM explosion protection 6DR4004-7J Alarm unit without explosion protection 6DR4004-8A Alarm unit with PTB explosion protection 6DR4004-6A Alarm unit with FM...
  • Page 261: Spare Parts

    Scope of delivery/spare parts/accessories 16.4 Spare parts 16.4 Spare parts Spare parts: Positioner SIPART PS2 Description Order number For version Plastic cover with 4 screws C73451-A430-D82 6DR4*** and circumferential sealing 6DR5*** ring. Metal cover with 4 screws C73451-A430-D83 66DR4*** and circumferential sealing 6DR5*** ring.
  • Page 262 Scope of delivery/spare parts/accessories 16.4 Spare parts Spare parts: Positioner SIPART PS2 Description Order number For version Potentiometer (complete) C73451-A430-D84 6DR4*** 6DR5*** 6DR40** can be used either after refining the two-wire input or the three/four-wire input. Note See catalog FI01 "Field device for process automation" for additives and possible modules. SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 263: Scope Of Delivery Of Small Part Sets

    Scope of delivery/spare parts/accessories 16.5 Scope of delivery of small part sets 16.5 Scope of delivery of small part sets Small part set 1 The small part set 1 with the order number C73451-A430-D85 contains the following items: Position Quantity [unit] Terminal strip C73451-A430-C21 Terminal strip C73451-A430-C22...
  • Page 264 Scope of delivery/spare parts/accessories 16.5 Scope of delivery of small part sets Small part set 2 The small part set 2 with the order number C73451-A430-D86 contains the following items: Position Quantity [unit] Clamping piece Pick-up bracket Screw DIN 7984 M6x25-A2 Spring lock washer DIN 127 B6-SN06031 Screw SN 62217 G4x45-/16WN1452-TX-ST Screw SN 62217 G4x14-combi-Torx-TX-ST...
  • Page 265: Accessories

    Scope of delivery/spare parts/accessories 16.6 Accessories 16.6 Accessories Accessories Order number Mounting kit for linear actuator IEC 534 - 6 including a lever for 3 ... 35 mm 6DR4004-8V actuator travel Additional lever for actuator travel > 35 to 130 mm 6DR4004-8L Mounting kit for part-turn actuators VDI/VDE 3845 6DR4004-8D...
  • Page 266 Scope of delivery/spare parts/accessories 16.6 Accessories SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 267: Appendix

    Bibliography/catalogs/standards A.1.1 Bibliography/catalogs/standards Bibliography and catalogs Title Publisher Order number SIMATIC NET, Ind. communication for Siemens AG E86060-K6710-A101-B5 automation and drives catalog, IK PI, 2007 Field devices for process automation Siemens AG E86060-K6201-A101-A8 catalog, FI 01, 2007 SIMATIC PCS 7 process control system...
  • Page 268: Sil Declaration Of Conformity

    Appendix A.2 SIL declaration of conformity SIL declaration of conformity SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 269: Test Report

    Appendix A.3 Test report Test report SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 270 Appendix A.3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 271 Appendix A.3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 272 Appendix A.3 Test report SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 273: Abbreviations

    Abbreviations List of abbreviations Abbreviation Long form Meaning Analog-to-digital converter Alternating current Alternating current Asset Management Solutions Communication software by Emerson Process comparable with the PDM Automatic Operating mode ATEX Atmosphère explosible Product and operation directive of European Commission for explosion protection.
  • Page 274 Abbreviations B.1 List of abbreviations Abbreviation Long form Meaning Process device manager Siemens communication software / engineering tool PROFIBUS Process field bus Fieldbus Physikalisch Technische Bundesanstalt Slotted initiator alarm unit Safety integrity level Safety requirement level as per IEC 61508/IEC 61511...
  • Page 275 Abbreviations B.1 List of abbreviations Abbreviation Full term in English Meaning MooN "M out of N" voting Classification and description of the safety-instrumented system in terms of redundancy and the selection procedures used. A safety-instrumented system or part that consists of "N" independent channels.
  • Page 276 Abbreviations B.1 List of abbreviations SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 277: Glossary

    Glossary Analog A signal type which represents data using continuously varying, measurable and physical quantities, e.g. current or voltage. Opposite to digital. The range between 4 and 20 mA is often used to transfer analog signals. Analog-to-digital converter An analog-to-digital converter is an interface between the analog environment and the digitally working computers.
  • Page 278 Glossary Configuration See parameterization. Cornerstone Management software for process instrumentation. Dangerous failure Failure with the potential to switch a safety-instrumented system to a hazardous or non- functioning safety status. Dangerous failure Failure with the potential to bring the safety-instrumented system into a dangerous or non- functional status.
  • Page 279 Glossary Device category 3 Category 3 devices must be procured such that they ensure a normal degree of safety. Devices in this category must ensure the required degree of safety in case of frequent faults or the ones that are normally expected, e.g. defects in the device, and prevent the ignition sources.
  • Page 280 Glossary Fieldbus A fieldbus is an industrial communication system used to connect a number of field devices with a control device. Field devices include measuring sensors, final controlling elements and actuators. Final controlling element Converter that converts electric signals into mechanical or other non-electric variables. Firmware Firmware (FW) is the software embedded in a chip in electronic devices.
  • Page 281 Glossary bus. HART implements the widely used 4/20 mA standard to transfer analog sensor signals. Existing cables of the old system can be used directly and both systems can be operated simultaneously. HART specifies several protocol levels in the OSI model. HART enables transfer of process and diagnostics information and control signals between field devices and superordinated control system.
  • Page 282 Mixture of air, combustible gases, vapors or mist. Process device manager PDM is a Siemens software package for project planning, parameterization, commissioning and maintenance of network configuration and field devices. Part of SIMATIC Step7. Used for the configuration and diagnostics of SIPART PS2.
  • Page 283 Glossary Protocols Protocols contain information about data formats, time sequences and error handling when exchanging data between computers. A protocol is a convention about establishing, monitoring and terminating a connection. Different protocols are required for a data connection. Protocols can be assigned to every layer of the reference model.
  • Page 284 Glossary The international standard IEC 61508 defines four discrete safety integrity levels (SIL) from SIL 1 to SIL 4. Every level indicates a probability range for the failure of the safety function. The higher the SIL of the safety-instrumented system, the higher the probability that the required safety function works.
  • Page 285 Glossary Zone 22 Zone 22 is an area in which a potentially explosive gaseous atmosphere in the form of a cloud of combustible dust in air never develops or develops only for a short while during normal operation. SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 286 Glossary SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 287: Index

    Index Parameter, 144 Documentation Edition, 11 Accessories, 256 Actuator medium Natural gas, 21 Actuator type Electrical connection Parameter, 142 Hazardous area, 13 Alarm function Enclosure, 255 Parameter, 151 End of the manipulated variable limit Angle of rotation of the feedback shaft Parameter, 147 Parameter, 143 Environmental protection, 12...
  • Page 288 Index History, 11 Description, 144 Parameters 6 to 53 Description, 145 Overview, 136 Parameters 7 and 8 Installation Description, 145 Iy module, 61 Positioner Intrinsic safety, 14 Dual-action part-turn actuator, 19 Iy module Single-action linear actuator, 19 Installation, 61 Positioner Single-action linear actuator, 18 SIPART PS2 PA with EEx d protection, 17 SIPART PS2 PA with EEx ia/ib protection, 17...
  • Page 289 Index PA, 32 Parameter, 147 Profile, 34 Station number Strand, 34 Parameter, 158 Topology, 32 Structure Purge air switch, 22, 29 Type plate, 20 Pz, 113 system Safety-instrumented, 107 System integration PDM, 11 Qualified personnel, 15 Technical data Positioner, 241 Recycling, 12 Terminating resistor, 35 Response threshold of fault message...
  • Page 290 Index SIPART PS2 with PROFIBUS communication Operating Instructions, 09/2007, A5E00127926-07...
  • Page 292 Siemens Aktiengesellschaft @ 1 P A 5 E 0 0 1 2 7 9 2 4 @ Automation and Drives (A&D) A5E00127926 Sensors and Communication Process Sensors 76181 KARLSRUHE GERMANY www.siemens.com/processinstrumentation A5E00127926-07...

Table of Contents