Automatic initialization of linear actuators

Requirements
The following conditions must be fulfilled before activating the automatic initialization:
1. The actuator spindle can be moved completely.
2. The actuator spindle is at a central position after moving.
Initializing the linear actuator automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press
configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset
settings in the "PRST" parameter.
1. Switch to the "Configuration" mode. To do this, press the
seconds. The display shows the following:
2. Call the "2.YAGL" parameter. To do this, briefly press the
shown on the display depending on the setting:
3. Check whether the value displayed in the "2.YAGL" parameter matches the setting of the
transmission ratio selector. If required, change the setting of the transmission ratio
selector to 33° or 90°.
SIPART PS2 with and without HART
Operating Instructions, 09/2014, A5E00074631-12
Commissioning
7.5 Commissioning linear actuators
. The settings
button for at least 5
button. The following is
125