Troubleshooting
Table 4-6 Fault Messages
Fault
Number Message
F58
FET2 Over
Temperature
Shutdown
F59
GOCFG process
failed
F63
AC Overload
F64
AC Overload L1
F65
AC Overload L2
F66
System
Configuration
Fault
F67
Watchdog Error
4–24
Fault Type
Cause
Automatic
See F57.
Manual
Auto-configuration
process failed.
Escalating
Excessive load on the AC
Auto Fault.
output.
Must occur
3 times in
5 minutes
before
becoming a
manual fault.
Escalating
Excessive load on the AC
Auto Fault.
output.
Must occur
3 times in
5 minutes
before
becoming a
manual fault.
Escalating
Excessive load on the AC
Auto Fault.
output.
Must occur
3 times in
5 minutes
before
becoming a
manual fault.
Automatic
Multi-Unit Configuration
settings are incorrect.
Manual
Solution
See F57.
Retry the "Copy From"
procedure, or configure the
unit manually.
Check for loads above the
inverter's capacity. Turn off
some loads if necessary. To
clear the fault:
Turn off the unit by holding
the power button for 5 sec.
Disconnect the Conext XW+
from the battery bank for 20
sec.
See F63
See F63.
Ensure only one unit is
configured as the master.
Ensure each unit has a
unique Device Number, and
that connections have been
configured correctly. Ensure
there is only one primary
charger. See "Connections
Menu" on page 3–45.
Service required.
975-0240-01-01