Table 4-6 Fault Messages
Fault
Number Message
F35
AI L2 Under
Voltage
F36
AI L1L2 Under
Voltage
F37
AI L1 Under
Voltage
F38
AI L2 Under
Voltage
F39
AI L1L2 Under
Voltage
F40
AI L1L2 Under
Voltage
F41
APS Under
Voltage
F42
APS Over Voltage
975-0240-01-01
Fault Type
Cause
Automatic
See F34.
Automatic
See F34.
Automatic
Under-voltage anti-
islanding, fast
disconnect, 66 VAC.
Automatic
See F37.
Automatic
Under-voltage anti-
islanding fault, caught by
the qualification limit,
voltage difference
between L1 and L2.
Automatic
Under-voltage anti-
islanding, fast
disconnect, 132 V.
Escalating
Auxiliary power supply
Auto Fault.
under-voltage shutdown
Must occur
3 times in
30 seconds
before
becoming a
manual fault.
Escalating
Auxiliary power supply
Auto Fault.
over-voltage shutdown
Must occur
3 times in
30 seconds
before
becoming a
manual fault.
Faults and Warnings
Solution
See F23.
See F23.
See F23.
See F23.
See F23.
See F23.
Clear the fault and attempt
restart. If problem persists,
call customer service.
Clear the fault and attempt
restart. If problem persists,
call customer service.