C Entric Specifications - Gamatronic CENTRIC 50 kW User Manual

Ups system
Hide thumbs Also See for CENTRIC 50 kW:
Table of Contents

Advertisement

13. C
ENTRIC SPECIFICATIONS
CENTRIC:
UPS SYSTEM SPECIFICATIONS
Topology
Operation
Input
Voltage (V)
Voltage tolerance (%)
Current (A)
Rectifier frequency (Hz)
Power walk-in (sec)
Power factor correction
THDI (%)
Inrush current
Bypass voltage tolerance (%)
Output
Rated Power (kVA/kW)
Nominal frequency (Hz)
Frequency tracking range (Hz)
Frequency tracking slew rate (Hz/sec)
Frequency (in free-running mode) (Hz)
Nominal voltage (Vac)
Static voltage regulation (%)
Regulation for 100 % unbalanced load (%)
Dynamic response to 100 % load step (%)
Overload withstand
Waveform
THD (%)
Load CF (max)
Power factor
Ac-Ac efficiency (nominal) (%)
Batteries
Dc-link voltage (Vdc)
Quantity
Type
General
Maximum power dissipation (Po=25 kW)
Ambient temperature (°C)
Relative humidity (%)
Altitude (m)
Enclosure
Cooling system
Design & manufacturing standards
Safety
EMC
Design classification
Low magnetic field radiation
Dimensions
UPS model
# of power modules
Power output (kW/kVA)
Height (mm) (w/o wheels)
Width (mm)
Depth (mm)
Weight (kg) w/o batt. box
Dimensions (H x W x D, mm) & weight of batt. box for 50 kW system
106
G
E
AMATRONIC
Table 14: Technical specifications
Inverter mode
Bypass mode
50 kW
1
2
2
25
50
50
665
72.2
92.0
102.4
All specifications are subject to change without advance notice.
I
L
LECTRONIC
NDUSTRIES
TD
Modular, double-conversion, VFI, on-line battery
Continuous
3x400 (4 wires + Gnd)
-20 / +15
(360 ~ 460 Vac: full power; 320 ~ 360 Vac: derated 20 %)
3 × 42 per module – no inrush current at startup
40 ~ 70
>60
>0.99
<3
None
±10 when synchronized; –10~–15 when unsynchronized
25 ~ 200
50/60
±(0.5, 1, 2, 3, 4), selectable
1
50/60 ±0.1 %
3x400 (4 wires + Gnd)
±1
±1
±2
110 % : 10 min, 125 % : 60 s, 150 % : 30 s
125 % : 10 min, 1000 % : 1 cycle
Sinusoidal
Linear load: <2; non-linear load: <6
6:1
Any
Up to 96
+/– 405
60 × 12 Vdc
Sealed, lead-acid. Lithium-ion batteries also supported.
N*1041 W (N*3552 BTU/h), where N = # modules
-10 to +40 (operating), -20 to +60 (storage)
95 maximum, non-condensing
1500 without derating
IP20
Multi-fan with speed control (forced)
IEC 62040-1
IEC 62040-2
IEC 62040-3
EMF as per ICNIRP
100 kW
3
4
4
75
100
100
932
540
757
122.2
142
149.3
985 x 540 x 743, 66 kg
.
200 kW
5
6
7
125
150
175
1200
169.1
188.9
208.7
CENTRIC User Guide, rel. 3.4
8
200
228.5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents