(Note: these registers can be addressed as either holding registers [for example, 4x0002] or input registers [for example, 3x0002])
Register
Variable name
1
4x0001
Battery Condition
2
4x0002
Battery Status
3
4x0003
Battery Charge
4
4x0004
Seconds On Battery
5
4x0005
Estimated Minutes
6
4x0006
Estimated Charge
7
4x0007
Battery Voltage
8
4x0008
Battery Current
9
4x0009
Battery Temperature
11
4x0011
Input Lines Number
12
4x0012
Input Frequency Line 1
13
4x0013
Input Voltage Line 1
14
4x0014
Input Current Line 1
16
4x0016
Input Frequency Line 2
17
4x0017
Input Voltage Line 2
18
4x0018
Input Current Line 2
20
4x0020
Input Frequency Line 3
21
4x0021
Input Voltage Line 3
22
4x0022
Input Current Line 3
G
E
AMATRONIC
LECTRONIC

Table 4: Holding Registers for Modbus queries

GET Values
0: Good
1: Weak
2: Replace
0: Battery OK
Has effect only during power failure (battery discharge), "Battery low" usually comes
1: Battery Low
minutes before the UPS batteries are depleted and it switches off
2: Battery Depleted
0: Floating
Most common situation is "floating" as a constant state, however this depends on the
1: Charging
UPS topology
2: Resting
3: Discharging
seconds
Has effect only during power failure
minutes
Mathematical estimation of available backup time
0-100%
Mathematical estimation of battery charge in percents
×10 Vdc
Divide the value by 10 for real measurement: 485/10=48.5 Vdc
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
°C
Degrees centigrade
1 to 3
Number of the UPS input phases
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
CENTRIC User Guide, 3.4
I
L
.
NDUSTRIES
TD
Remarks