The default port of 262 will be acceptable in most environments. In the case that port 262 is not available
on the shutdown target computer (for example, if an application on the target computer requires exclusive
use of that port), a different port may be used.
To apply your changes, press the arrow in the upper left corner of the screen (see Figure 34).
To abandon your changes, press the "Connectivity" icon.

Figure 34: Shutdown destination screen

7.2.6.6
EMAIL CONFIGURATION (OPTIONAL FEATURE)
You can have the Centric send email messages to the email addresses of your choice, containing
information about the starting and ending of system alarms.
The message body contains:
a timestamp,
the user-assigned priority of the message (Informational / Warning / Critical),
the main message text as it appears in the log,
the status of the log message: "On" (alarm condition started) or "Off" (alarm condition ended).
Figure 35: Example of email message body
CENTRIC User Guide, rel. 3.4