UPS shutdown by Emergency Power Off
UPS shutdown by end of battery backup
UPS shutdown by hardware "Off" button
UPS shutdown by overload
UPS shutdown by remote user command
Figure 45 shows output dry contact #6 defined to change state when the Centric moves into or out of
bypass mode. The move to bypass generates an alarm, and in this example dry contact #6 is linked to that
alarm.

Figure 45: Example of an output dry contact linked to an alarm

7.2.9.2.1 L
OCATION OF THE OUTPUT DRY CONTACTS
The connections for the output dry contacts are located in two locations on the upper rear panel of the
UPS. See items 1 and 2 in Figure 62, and also Figure 63 and Figure 64.
7.2.9.2.2 C
ONNECTING OUTPUT DRY CONTACTS
The connections for output dry contacts 1 and 2 consist of pins on the D9 alarm connector on the upper
right side of the Centric rear panel (connector group 2 – see Figure 62 and Table 9.
The connection for output dry contact 1 is pin 5 and pin 4 (the COMMON pin) on the D9 alarm connector.
Output dry contact 1 is Normally Open.
The connection for output dry contact 2 is pin 3 and pin 4 on the D9 alarm connector. Output dry contact 2
is Normally Open.
The factory default association of output dry contact 1 is the "Battery low" alarm. The factory default
association of output dry contact 2 is the "Ac input failure" alarm. These associations can be changed if the
user so desires.
CENTRIC User Guide, rel. 3.4
G
E
AMATRONIC
LECTRONIC
1
2
AND
I
L
.
NDUSTRIES
TD
63