Gamatronic CENTRIC 50 kW User Manual page 54

Ups system
Hide thumbs Also See for CENTRIC 50 kW:
Table of Contents

Advertisement

Register
Variable name
260
4x0260
Output Voltage Line 2
261
4x0261
Output Current Line 2
262
4x0262
Output Power Line 2
263
4x0263
Output Apparent Power Line 2
264
4x0264
Output Power Factor Line 2
265
4x0265
Output Load Line 2
266
4x0266
Output Voltage Line 3
267
4x0267
Output Current Line 3
268
4x0268
Output Power Line 3
269
4x0269
Output Apparent Power Line 3
270
4x0270
Output Power Factor Line 3
271
4x0271
Output Load Line 3
272
4x0272
Bypass Frequency
273
4x0273
Bypass Voltage Line 1
274
4x0274
Bypass Current Line 1
275
4x0275
Bypass Apparent Power Line 1
276
4x0276
Bypass Voltage Line 2
277
4x0277
Bypass Current Line 2
278
4x0278
Bypass Apparent Power Line 2
279
4x0279
Bypass Voltage Line 3
280
4x0280
Bypass Current Line 3
281
4x0281
Bypass Apparent Power Line 3
282
4x0282
Active Alarms Count
Register
Variable name
301
4x0301
General Fault
G
E
AMATRONIC
LECTRONIC
GET Values
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
%
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
%
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
Active alarms, except for the ones marked "ignored" or "for log only" in the controller
configuration
GET Values
0: Alarm off
Any active alarm exists, except for the ones marked "ignored" or "for log only" in the
1: Alarm on
controller configuration
46
I
L
.
NDUSTRIES
TD
Remarks
Remarks
CENTRIC User Guide, rel. 3.4