Technical Specifications; Table 5: Technical Specifications - Gamatronic g-net 101010002U-SD User Manual

1 kva / 2 kva / 3 kva online uninterruptible power system 19" rack-mount model
Table of Contents

Advertisement

8.
T
ECHNICAL
G-NET 19-INCH MODELS
I
NPUT
Voltage (Vac)
Nominal voltage (Vac)
Maximum current (A)
Rated frequency (Hz)
Frequency range (Hz)
O
UTPUT
Voltage (Vac)
Frequency (Hz)
Waveform
Power
THD (full load, %)
Overload tolerance
Ratio max. / normal load (crest ratio)
Transfer times (msec.)
- To/from battery
- To/from bypass (typical / max.)
O
E
PERATING
NVIRONMENT
Temperature
- Operation
- Storage
Humidity (%)
Altitude (m)
Standards:
B
ATTERIES
Type
Voltage
C
OMMUNICATION
RS232
D
IMENSIONS
UPS: W x H x D (mm)
UPS weight (kg)
Battery box: W x H x D (mm)
Batt. box weight (kg) incl. batteries (appx.)
10
G
E
AMATRONIC
LECTRONIC
S
PECIFICATIONS

Table 5: Technical Specifications

110 ~ 300, single phase, ground connection required
1000 VA, 800 W
Linear load)
Non-linear load
24+6=30

Technical Specifications

I
L
.
NDUSTRIES
TD
1000 VA
2000 VA
220/230
6
50 / 60
45 ~ 65
220 / 230 ±3 %
50 / 60 ±0.5 %
Sinusoid
2000 VA, 1600 W
<3 %
<6 %
105 % ~ 130 % : moves to bypass after 30 sec.;
over 130 % : moves to bypass after 200 ms
3:1
2.5 / <4
0 ~ +40 °C
-25 ~ +55 °C (w/o batteries)
Up to 95 (non-condensing)
<1500 without derating
EN62042-2:2006,
EN61000-3-2:2006+A1:2009+A2,
EN61000-3-3:2008
Sealed, lead-acid, maintenance free. 12 V per block
36 Vdc
72 Vdc
D9 connector
482 x 88 x 450
9
482 x 88 x 450
24+13=37
3000 VA
12
16
3000 VA, 2400 W
0
96 Vdc
11
24+17=41
G-NET 19" UPS User Manual
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

G-net 101020002u-sdG-net 101030002u-sd

Table of Contents