Power + Premium Specifications; Table 5: System Technical Specifications - Gamatronic POWER+ PREMIUM Installation Manual

Table of Contents

Advertisement

+ P
12. P
OWER
Topology
Construction
Operation
Input
Nominal voltage (Vac)
Voltage range (%)
Nominal current (A)
Frequency (Hz)
Power walk-in (s)
Power factor correction
THDI (%)
Output
Rated power (kVA / kW)
Nominal voltage (Vac)
Frequency, in free-running mode (Hz)
Frequency tracking range (Hz)
Frequency tracking slew rate (Hz/sec)
Static regulation (%)
Regulation for unbalanced load (%)
Dynamic response to 100 % load step (%)
Overload withstand
Waveform
THD (%)
Load CF (max)
Ac-Ac efficiency, nominal (%)
Dc-Ac efficiency, nominal (%)
Batteries
Dc-link voltage (Vdc)
Quantity and type
General
Maximum power dissipation (Po=10 kW)
Fuse clearance capability
Ambient temperature (°C)
Relative humidity (%)
Altitude (m)
Enclosure
Cooling system
Standards
Safety
EMC
Design
Low magnetic field radiation
Dimensions
Weight of single power module (kg)
UPS type
Height (cm)
Width (cm)
Depth (cm)
Weight (kg)
Acoustic Noise
Noise (dBA) with half load
Noise (dBA) with full load
Power + PREMIUM, Installation Guide, rel. 1.7
G
AMATRONIC
REMIUM SPECIFICATIONS

Table 5: System technical specifications

Inverter mode
Bypass mode
10 kVA
20 kVA
30 kVA
71
80
90
98
113
128
48
52
53
51
54
55
All specifications are subject to change without advance notice.
E
I
L
LECTRONIC
NDUSTRIES
TD
On line battery, double-conversion, VFI
Modular, parallel hot-plugged modules
Continuous
3×400 (4 wires + Gnd)
–22 / +15
3 × 15 per module, no inrush current at startup
47 ~ 63
1 to 30 in 1 s increments
0.99
5
Up to 100
3x400 (4 wires + Gnd)
50/60 ±0.1 %
±0.5, ±1, ±2, ±3, +4 (selectable)
1
±1
±2 for 100 % unbalanced load
±2
110 % : 10 minutes, 125 % : 60 seconds, 1000 % : 1 cycle
125 % : 10 minutes
Sinusoidal
Less than 2 for linear load
6:1
Up to 96
Up to 98
±320 to ±405
60 × 12 Vdc, sealed, lead acid, rechargeable
N*416 W (N*1420 BTU), where N = # modules
Input, output, dc link
-10 to +40 (operating), -20 to +60 (storage)
95 maximum, non-condensing
1500 without derating
IP20
Forced air: multi-fan with speed control
IEC 62040-1
IEC 62040-2
IEC 62040-3
EMF as per ICNIRP
9.8
40 kVA
50 kVA
60 kVA
99
108
118
59.8
67.3
143
158
173
54
55
55.8
57
58
58.8
.
70 kVA
80 kVA
127
136
188
203
56.4
57
59.4
60
90 kVA
100 kVA
146
155
218
233
57.5
58
60.5
61