9. TECHNICAL SPECIFICATIONS

INPUT
3 Phase
Voltage range
Frequency
Power walk-in
Required ext. MCB (A) :
Input PF
OUTPUT
Voltage (V)
Power
Efficiency
Dissipation at full load
Voltage regulation
Frequency tracking range
Slew rate
Overload
Load P.F.
Waveform
Crest factor
Total harmonic distortion
Protection
Dynamic response to 100% load change
Transition time :
To and from line
Phase deviation
Rejection ratio
Leakage current
BACKUP OPERATION
Backup time
DC voltage
Batteries (internal)
Battery recharge time
Expected battery life
COMMUNICATION OPTIONS
RS232C
Alarm
Remote indication panel
SNMP
Speech dialer
µPS Series 3:3 Phase 10kVA (GEMS)
Technical Specifications
(1)
125%
150%
User Guide
3 x 208 Vac
+10%-20%
57 - 63Hz
12 sec.
3 x 40
0.97
3 X 208 Vac
10kVA/8Kw
>87%
880W/260BTU
± 1%
± 1, ± 2, ± 3Hz (selectable)
1 Hz/sec.
10 minutes
30 seconds
0.8
Sinusoidal
3:1
Less than 2% (at linear load)
Overload and short circuit
2%
Less than 0.5 ms
Balanced load ± 1
More than 100 dB
< 3mA
45Mins @ 2KW
176Vdc
13 × 12Vdc 20Ah
Sealed Lead-Acid
Approximately 6-8 hours
10-12 years
Shutdown, monitor
Shutdown software
Optional
Included
Optional
Page 47
o

Hide quick links:

Advertisement

Table of Contents
loading