Single Ups Module Specifications; Table 2-1 Single Ups Module Specifications - Gamatronic POWER PLUS Technical Manual

Modular ups system 10 kva to 100 kva, 3x400 v
Table of Contents

Advertisement

Gamatronic Electronic Industries Ltd.
2.1.1

SINGLE UPS MODULE SPECIFICATIONS

Output Rated Power
Topology
Construction
Input Voltage (V)
Input Voltage range (%)
Input Current (A)
Input Frequency (Hz)
Frequency tracking range (Hz)
Output slew rate
Power walk-in (sec)
Input Power Factor
Input THDI (%)
Output Voltage (V)
Output Static Regulation (%)
Output Regulation for unbalanced load (%)
Dynamic response to 100% load step (%)
Overload
Output Waveform
Output THD (%)
Load CF (max)
Fuse clearance capability
AC-AC efficiency (nominal)
Maximum power dissipation (Po=8KW)
Ambient temperature (ºC)
Relative humidity (%)
Altitude (m)
DC-Link Voltage
Cooling system
Dimensions: W x H x D
Weight
Power+ Technical Guide

Table 2-1 Single UPS Module Specifications

TECHNICAL DATA – UPS MODULE
-27 and +20
10 kVA / 8 kW
Online Battery, Double Conversion
Modular parallel hot-plugged modules
3 × 400+N (3 × 230 V)
15 A
47–63 Hz
±1, ±2, ±3 (selectable)
1 Hz/sec
> 60
0.99
5
3 × 400+N (3 × 230V)
±1
±1 for 100% unbalanced load
2
110 % for 10 minutes
125 % for 60 seconds
1000 % for 1 cycle
Sinusoidal
Less than 2 for linear load
6:1
Input, Output, DC link
Up to 96 at full load
421 W (1437 BTU)
-10 to +40 (operating)
-20 to +60 (storage)
95 max non-condensing
1500 w/o de-rating
±340 V to ±425 V
Forced air: multi-fan with speed control
19" x 2U x 455 mm (Excluding shelf)
9.5 Kg
9