Gamatronic CENTRIC 50 kW User Manual page 50

Ups system
Hide thumbs Also See for CENTRIC 50 kW:
Table of Contents

Advertisement

Register
Variable name
24
4x0024
Output Source
25
4x0025
Output Frequency
26
4x0026
Output Number Of Lines
27
4x0027
Output Voltage Line 1
28
4x0028
Output Current Line 1
30
4x0030
Output Load Line 1
31
4x0031
Output Voltage Line 2
32
4x0032
Output Current Line 2
34
4x0034
Output Load Line 2
35
4x0035
Output Voltage Line 3
36
4x0036
Output Current Line 3
38
4x0038
Output Load Line 3
39
4x0039
Bypass Frequency
40
4x0040
Bypass Number Of Lines
41
4x0041
Bypass Voltage Line 1
42
4x0042
Bypass Current Line 1
44
4x0044
Bypass Voltage Line 2
45
4x0045
Bypass Current Line 2
47
4x0047
Bypass Voltage Line 3
48
4x0048
Bypass Current Line 3
50
4x0050
Temperature Alarm
G
E
AMATRONIC
LECTRONIC
GET Values
0: Normal
Depends on the UPS topology
1: On Battery
2: On Bypass
3: Reducing
4: Boosting
5: Other
6: None
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
1 to 3
Number of the UPS output phases
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
%
Some units might show values over 100% in case of overload
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
%
Some units might show values over 100% in case of overload
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
%
Some units might show values over 100% in case of overload
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
1 to 3
Number of the UPS bypass phases
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
0: Alarm off
1: Alarm on
42
I
L
.
NDUSTRIES
TD
Remarks
CENTRIC User Guide, rel. 3.4