2.3

System controller

The Centric system controller has three purposes:
Controls and monitors the operation of the Centric according to the user's commands.
Collects and summarizes data from all sections of the UPS.
Manages communication with external computers for data transfer and operation.
The Centric can operate without the system controller but with reduced functionality.
2.4
UPS module (25 kVA / 25 kW)
The UPS module is the core of the Centric , which consists of from one to eight identical internal modules
operating in parallel.
Each UPS module includes a 3-phase charger with PFC (power factor correction) and a 3-phase PWM
(pulse-width modulation) inverter connected to batteries by a classic dc link.
2.5
Static switch module
The centralized hybrid static switch enables an automatic transfer of the load from the output of the
inverters to an alternate source – the ac mains, for example – when the inverter is unable to supply
sufficient power to the load (for example, in the event of an overload, or an inverter failure). The static
switch transfers high currents at very high speed; a typical transfer time is 3 ms.
2.6
Battery
The Centric battery bank provides backup power to the UPS and its load devices in the event that the
utility ac input fails. The batteries are housed in an external cabinet adjacent to the Centric . (The Centric
can also be placed on top of the battery cabinet.) The batteries are charged by the rectifier that supplies
both the inverter and the battery charger.
The Centric supports the use of standard lead-acid batteries, and also lithium-ion batteries. If you plan to
use lithium-ion batteries, consult with your dealer to be sure that the battery setup parameter values are
appropriate for the batteries you will be using.
The battery cabinet should be installed as close to the UPS as is practically possible.
Fast-acting fuses (semiconductor fuses) must be used between the battery and the UPS.
Protect the batteries from moisture, dampness, and foreign substances.
The temperature of the battery's surroundings influences the batteries' useful lifetime.
Table 1: Battery lifetime vs. environmental temperature as per Eurobat
CENTRIC User Guide, rel. 3.4
G
E
AMATRONIC
LECTRONIC
E
NVIRONMENTAL
TEMPERATURE
20 °C
30 °C
40 °C
I
L
.
NDUSTRIES
TD
A
CHIEVABLE PERCENTAGE OF
'
BATTERY
S RATED LIFETIME
100 %
50 %
20 %
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents