6.
Navigate to the "Detail 2" window ("Status > Modules > Detail 2").
When the output of the module is disconnected or the inverter is shut down, the measured voltages
must be in the range 2.45 – 2.54 V.
7.
Verify that measured dc voltage is within the range 400 – 410 V, when ac input is normal and the
battery is charged.