13. Centric specifications

System specifications for the CENTRIC 3x480 Vac modular UPS
Topology
Operation
Input
Voltage (Vac)
Voltage range (%)
Current (A)
Rectifier frequency (Hz)
Power factor correction
THDI (%)
Inrush current
Bypass voltage tolerance (%)
Output
Rated power (kVA / kW)
Nominal frequency (Hz)
Frequency tracking range (Hz)
Frequency tracking slew rate (Hz/sec)
Frequency in free-running mode (Hz)
Nominal voltage (Vac)
Static voltage regulation (%)
Regulation for unbalanced load (%)
Dynamic response to 100 % load step (%)
Overload withstand
Waveform
THD (%)
Load CF (max)
Ac-ac efficiency, nominal
Batteries
Nominal voltage (Vdc)
Charging voltage (Vdc)
Quantity
Type
General
Maximum power dissipation (W, Po=30 kW)
Ambient temperature
Relative humidity (%)
Altitude (m)
Enclosure
Cooling system
Design & manufacturing standards
Safety
EMC
Design classification
Low magnetic field radiation
Dimensions
# of power modules
Power output (kW)
Weight (kg)
Height, Width, Depth (mm / in)
84
G
E
AMATRONIC
LECTRONIC

Table 17: Technical specifications

Modular, double-conversion, VFI
Continuous
3x480 Vac, 4 wires + Gnd or 3 wires + Gnd
+10 / -15
3x38 per module – no inrush current at startup
40 ~ 70
>0.99
<3
None
±10 when synchronized; –10 to –15 when unsynchronized
120 / 120, 240 / 240
50/60
±(0.5, 1, 2, 3, 4) selectable
1
50/60, ±0.1 %
3x480 Vac, 4 wires + Gnd or 3 wires + Gnd
±1
±1 for 100 % unbalanced load
±2
Inverter mode
110 % : 10 min, 125 % : 60 s, 150 % : 30 s
Bypass mode
125 % : 10 min, 1000 % : 1 cycle
Sinusoidal
Linear load: <2; non-linear load: <6
6:1
Up to 96
480 (240 pole-to-midpoint)
540 (270 pole-to-midpoint)
2 x 20 × 12 Vdc
Sealed, lead acid, rechargeable, maintenance-free
N*1217 W (N*4153 BTU/h), where N = # modules
(°C)
-10 ~ +40 (operating), -20 ~ +60 (storage)
(°F)
+14 ~ +104 (operating), -4 ~ +140 (storage)
95, maximum, non-condensing
1500 without derating
IP20
Multi-fan with speed control (forced)
UL 1778 (4
FCC part 15/B, IEC 62040-2
IEC 62040-3
EMF as per ICNIRP
1
2
3
30
60
90
206.1
224.8
264.5
H=2015 / 79.4; W=600 / 23.6;
All specifications are subject to change without notice.
I
L
.
NDUSTRIES
TD
th
edition), IEC 62040-1
4
5
120
150
180
283.2
322.9
341.6
D=1000 / 39.5
Centric 3x480 Vac, Installation Guide, rel. 2.2
6
7
8
210
240
381.3
400