Gamatronic CENTRIC 50 kW User Manual page 52

Ups system
Hide thumbs Also See for CENTRIC 50 kW:
Table of Contents

Advertisement

Register
Variable name
210
4x0210
Seconds On Battery
211
4x0211
Estimated Backup Time
212
4x0212
Estimated Charge
213
4x0213
DC Voltage positive
214
4x0214
DC Voltage Negative
215
4x0215
DC Voltage total
216
4x0216
Battery Current
217
4x0217
Battery Temperature
218
4x0218
Number of phases
219
4x0219
Inverter Frequency Line 1
220
4x0220
Inverter Voltage Line 1
221
4x0221
Inverter Current Line 1
222
4x0222
Inverter Power Line 1
223
4x0223
Inverter Apparent Power Line 1 ×10 KVA
224
4x0224
Inverter Frequency Line 2
225
4x0225
Inverter Voltage Line 2
226
4x0226
Inverter Current Line 2
227
4x0227
Inverter Power Line 2
228
4x0228
Inverter Apparent Power Line 2 ×10 KVA
229
4x0229
Inverter Frequency Line 3
230
4x0230
Inverter Voltage Line 3
231
4x0231
Inverter Current Line 3
232
4x0232
Inverter Power Line 3
233
4x0233
Inverter Apparent Power Line 3 ×10 KVA
234
4x0234
Charger Voltage Line 1
G
E
AMATRONIC
LECTRONIC
GET Values
Seconds
Only available during power failure, otherwise zero
Minutes
Only available during power failure and when the battery is fully charged (6 in 4x0209),
otherwise zero. This value is a rough approximation received by mathematical
calculations, and assumes new and healthy batteries of average VRLA type in initial fully
charged state.
0-100%
Mathematical calculation of battery charge in percents; will send 200 if no value has been
calculated
×10 Vdc
Divide the value by 10 for real measurement: 4051/10=405.1 Vdc
×10 Vdc
Divide the value by 10 for real measurement: 4051/10=405.1 Vdc
×10 Vdc
Divide the value by 10 for real measurement: 8102/10=810.2 Vdc
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
°C
Degrees centigrade
1 to 3
Number of the UPS phases (always 3 for current units)
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
44
I
L
.
NDUSTRIES
TD
Remarks
CENTRIC User Guide, rel. 3.4