5 SETTINGS
a) MAIN MENU
PATH: SETTINGS
CONTROL ELEMENTS
MONITORING
ELEMENTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
b) BREAKER ARCING CURRENT
PATH: SETTINGS
CONTROL ELEMENTS
BREAKER 1
ARCING CURRENT
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
MONITORING ELEMENTS
BREAKER 1
ARCING CURRENT
BREAKER 2
ARCING CURRENT
CT FAILURE
DETECTOR
VT FUSE FAILURE 1
VT FUSE FAILURE 2
BROKEN CONDUCTOR 1
BROKEN CONDUCTOR 2
THERMAL OVERLOAD
PROTECTION
MONITORING ELEMENTS
BKR 1 ARC AMP
FUNCTION: Disabled
BKR 1 ARC AMP
SOURCE: SRC 1
BKR 1 ARC AMP INT-A:
Off
BKR 1 ARC AMP INT-B:
Off
BKR 1 ARC AMP INT-C:
Off
BKR 1 ARC AMP
DELAY:
0.000 s
BKR 1 ARC AMP LIMIT:
1000 kA2-cyc
BKR 1 ARC AMP BLOCK:
Off
BKR 1 ARC AMP
TARGET: Self-reset
BKR 1 ARC AMP
EVENTS: Disabled
L30 Line Current Differential System
5.7 CONTROL ELEMENTS
5.7.10 MONITORING ELEMENTS
See page 5–223.
See page 5–223.
See page 5–226.
See page 5–227.
See page 5–227.
See page 5–229.
See page 5–229.
See page 5–231.
BREAKER 1(2) ARCING CURRENT
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
2
Range: 0 to 50000 kA
-cycle in steps of 1
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5
5-223