Monitoring Elements - GE B90 Instruction Manual

Ur series low impedance bus differential system
Hide thumbs Also See for B90:
Table of Contents

Advertisement

5.6 CONTROL ELEMENTS
The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and
solid-state contact with voltage monitoring.
NOTE
a) MAIN MENU

PATH: SETTINGS
CONTROL ELEMENTS
 MONITORING
5
 ELEMENTS
b) CT TROUBLE ZONE

PATH: SETTINGS
CONTROL ELEMENTS
 CT TROUBLE ZONE 1
The CT Trouble feature is available only when
5-110
Figure 5–54: TRIP CIRCUIT EXAMPLE 2


MONITORING ELEMENTS

 CT TROUBLE ZONE 1
 CT TROUBLE ZONE 2
MESSAGE
 CT TROUBLE ZONE 3
MESSAGE
 CT TROUBLE ZONE 4
MESSAGE
 BUS REPLICA
MESSAGE

MONITORING ELEMENTS
CT TROUBLE ZONE 1
FUNCTION: Disabled
CT TROUBLE ZONE 1
MESSAGE
PICKUP: 0.100 pu
CT TROUBLE ZONE 1
MESSAGE
DELAY: 1.0 s
CT TROUBLE ZONE 1
MESSAGE
TARGET: Self-reset
CT TROUBLE ZONE 1
MESSAGE
EVENTS: Disabled
PRODUCT SETUP
B90 Low Impedance Bus Differential System
5.6.5 MONITORING ELEMENTS
See page 5–110.
See page 5–110.
See page 5–110.
See page 5–110.
See page 5–111.
CT TROUBLE ZONE 1(4)
Range: Disabled, Enabled
Range: 0.020 to 2.000 pu in steps of 0.001
Range: 1.0 to 60.0 s in steps of 0.1
Range:
Self-reset, Latched, Disabled
Range: Disabled, Enabled
B90 FUNCTION
B90 FUNCTION
5 SETTINGS
is set to "Protection".