GE L30 Instruction Manual page 527

Ur series line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 29 of 60)
ADDR
REGISTER NAME
5E74
CT Fail 1 Voltage Pickup
5E75
CT Fail 1 Pickup Delay
5E76
CT Fail 1 Target
5E77
CT Fail 1 Events
5E78
...Repeated for CT Fail 2
5E84
...Repeated for CT Fail 3
5E90
...Repeated for CT Fail 4
5E9C
...Repeated for CT Fail 5
5EA8
...Repeated for CT Fail 6
Stub Bus (Read/Write Grouped Setting)
5F10
Stub Bus Function
5F11
Stub Bus Disconnect
5F13
Stub Bus Trigger
5F15
Stub Bus Target
5F17
Stub Bus Events
50DD Disturbance Detection (Read/Write Grouped Setting)
5F20
50DD Function
5F21
50DD Non Current Supervision
5F23
50DD Control Logic
5F25
50DD Logic Seal In
5F27
50DD Events
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
5F71
Setting Groups Block
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
5F7D
Setting Group Function
5F7E
Setting Group Events
Setting Groups (Read Only)
5F7F
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Current Differential 87L (Read/Write Grouped Setting)
6000
87L Current Differential Function
6001
87L Current Differential Block
6003
87L Current Differential Signal Source 1
6004
87L Minimum Phase Current Sensitivity
6005
87L Current Differential Tap Setting
6006
87L Current Differential Phase Percent Restraint 1
6007
87L Current Differential Phase Percent Restraint 2
6008
87L Current Differential Phase Dual Slope Breakpoint
6009
87L Current Differential Ground Function
600A
87L Current Differential Ground Pickup
600B
87L Current Differential Ground Restraint
600C
87L Current Differential Ground Delay
600D
87L Current Differential Key DTT
600E
87L Current Differential External Key DTT
6010
87L Current Differential Target
6011
87L Current Differential Event
GE Multilin
RANGE
0 to 2
0 to 65.535
0 to 2
0 to 1
0 to 1
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 5
0 to 4294967295
0 to 4294967295
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 1
0 to 4294967295
0 to 5
0.1 to 4
0.2 to 5
1 to 50
1 to 70
0 to 20
0 to 1
0.05 to 1
1 to 50
0 to 5
0 to 1
0 to 4294967295
0 to 2
0 to 1
L30 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
pu
0.01
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F102
---
1
F300
---
1
F167
pu
0.01
F001
---
0.01
F001
%
1
F001
%
1
F001
pu
0.1
F001
---
1
F102
pu
0.01
F001
%
1
F001
seconds
0.01
F001
---
1
F102
---
1
F300
---
1
F109
---
1
F102
DEFAULT
20
1000
0 (Self-reset)
0 (Disabled)
B
0 (Disabled)
0
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
0
0
0 (Disabled)
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (Disabled)
0
0 (SRC 1)
20
100
30
50
10
0 (Disabled)
10
25
10
1 (Enabled)
0
0 (Self-reset)
0 (Disabled)
B-37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents