GE L30 Instruction Manual page 517

Ur series line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 19 of 60)
ADDR
REGISTER NAME
4083
RS485 Com1 Baud Rate
4084
RS485 Com1 Parity
4085
RS485 Com2 Baud Rate
4086
RS485 Com2 Parity
4087
Port 1 IP Address
4089
Port 1 IP Subnet Mask
408B
Port 1 Gateway IP Address
408D
Network Address NSAP
4097
Port 1 Link Loss Alert
4098
Port 2 Link Loss Alert
4099
Port 3 Link Loss Alert
409A
DNP Channel 1 Port
409B
DNP Channel 2 Port
409C
DNP Address
409E
DNP Client Addresses (2 items)
40A3
TCP Port Number for the Modbus Protocol
40A4
TCP/UDP Port Number for the DNP Protocol
40A5
TCP Port Number for the HTTP (Web Server) Protocol
40A6
Main UDP Port Number for the TFTP Protocol
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means "automatic") (2 items)
40A9
DNP Unsolicited Responses Function
40AA
DNP Unsolicited Responses Timeout
40AB
DNP Unsolicited Responses Maximum Retries
40AC
DNP Unsolicited Responses Destination Address
40AD
Ethernet Operation Mode
40AE
DNP Current Scale Factor
40AF
DNP Voltage Scale Factor
40B0
DNP Power Scale Factor
40B1
DNP Energy Scale Factor
40B2
DNP Power Scale Factor
40B3
DNP Other Scale Factor
40B4
DNP Current Default Deadband
40B6
DNP Voltage Default Deadband
40B8
DNP Power Default Deadband
40BA
DNP Energy Default Deadband
40BC
DNP Power Factor Default Deadband
40BE
DNP Other Default Deadband
40C0
DNP IIN Time Synchronization Bit Period
40C1
DNP Message Fragment Size
40C2
DNP Client Address 3
40C4
DNP Client Address 4
40C6
DNP Client Address 5
40C8
DNP Number of Paired Binary Output Control Points
40C9
DNP TCP Connection Timeout
40CA
DNP Communications Reserved (22 items)
40E0
TCP Port Number for the IEC 60870-5-104 Protocol
40E1
IEC 60870-5-104 Protocol Function
40E2
IEC 60870-5-104 Protocol Common Address of ASDU
40E3
IEC 60870-5-104 Protocol Cyclic Data Transmission Period
40E4
IEC 60870-5-104 Current Default Threshold
40E6
IEC 60870-5-104 Voltage Default Threshold
40E8
IEC 60870-5-104 Power Default Threshold
40EA
IEC 60870-5-104 Energy Default Threshold
GE Multilin
RANGE
0 to 11
0 to 2
0 to 11
0 to 2
0 to 4294967295
0 to 4294967295
0 to 4294967295
---
0 to 1
0 to 1
0 to 1
0 to 5
0 to 5
0 to 65519
0 to 4294967295
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 60
1 to 255
0 to 65519
0 to 1
0 to 8
0 to 8
0 to 8
0 to 8
0 to 8
0 to 8
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
1 to 10080
30 to 2048
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 32
10 to 7200
0 to 1
0 to 65535
0 to 1
0 to 65535
1 to 65535
0 to 100000000
0 to 100000000
0 to 100000000
0 to 100000000
L30 Line Current Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F112
---
1
F113
---
1
F112
---
1
F113
---
1
F003
---
1
F003
---
1
F003
---
---
F074
---
1
F102
---
1
F102
---
1
F102
---
1
F177
---
1
F177
---
1
F001
---
1
F003
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F102
s
1
F001
---
1
F001
---
1
F001
---
1
F192
1 (Full-Duplex)
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F003
---
1
F003
---
1
F003
---
1
F003
--
1
F003
---
1
F003
min
1
F001
---
1
F001
---
1
F003
---
1
F003
---
1
F003
---
1
F001
s
1
F001
---
1
F001
---
1
F001
---
1
F102
---
1
F001
s
1
F001
---
1
F003
---
1
F003
---
1
F003
---
1
F003
DEFAULT
8 (115200)
0 (None)
8 (115200)
0 (None)
2130706433
B
4294966272
56554497
0
0 (Disabled)
0 (Disabled)
0 (Disabled)
0 (None)
0 (None)
1
0
502
20000
80
69
0
0 (Disabled)
5
10
1
2 (1)
2 (1)
2 (1)
2 (1)
2 (1)
2 (1)
30000
30000
30000
30000
30000
30000
1440
240
0
0
0
0
120
0
2404
0 (Disabled)
0
60
30000
30000
30000
30000
B-27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents