GE L30 Instruction Manual page 146

Ur series line current differential system
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5.2 PRODUCT SETUP
To gain write access to a "Restricted" setting, program the
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the "Restricted" level according
to the access level timeout setting values.
If the setting and command passwords are identical, then this one password allows access to both commands and
settings.
NOTE
If a remote connection is established, local passcodes are not visible.
NOTE
REMOTE PASSWORDS
The remote password settings are visible only from a remote connection via the EnerVista UR Setup software.
Proper passwords are required to enable each command or setting level access.
To set the command or setting password:
1.
In the EnerVista software, navigate to Settings > Product Setup > Security menu item to open the remote password
settings window.
2.
Click the command or setting password Change button.
3.
Enter the new password in the New Password field. Requirements are outlined in the Password Requirements section
at the beginning of the chapter. When an original password has already been used, enter it in the Enter Password
field and click the Send Password to Device button.
4.
Re-enter the password in the Confirm Password field.
5
5.
Click the OK button. The password is checked to ensure that is meets requirements.
If you establish a local connection to the relay (serial), you cannot view remote passcodes.
NOTE
ACCESS SUPERVISION
PATH: SETTINGS
PRODUCT SETUP
 ACCESS
 SUPERVISION
The following access supervision settings are available.
INVALID ATTEMPTS BEFORE LOCKOUT: This setting specifies the number of times an incorrect password can be
entered within a three-minute time span before lockout occurs. When lockout occurs, the
REMOTE ACCESS DENIED
expiration of the lockout.
5-10

SECURITY
ACCESS SUPERVISION
 ACCESS LEVEL
 TIMEOUTS
INVALID ATTEMPTS
MESSAGE
BEFORE LOCKOUT: 3
PASSWORD LOCKOUT
MESSAGE
DURATION: 5 min
FlexLogic operands are set to "On". These operands are returned to the "Off" state upon
L30 Line Current Differential System
setting in the main security menu to "Setting" and
ACCESS LEVEL
Range: 2 to 5 in steps of 1
Range: 5 to 60 minutes in steps of 1
5 SETTINGS
or
LOCAL ACCESS DENIED
GE Multilin