5 SETTINGS
DEFAULT MESSAGE INTENSITY: To extend phosphor life in the vacuum fluorescent display, the brightness can be
attenuated during default message display. During keypad interrogation, the display always operates at full brightness.
SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME: These settings are only visible if the L30 has a liquid
crystal display (LCD) and control its backlighting. When the
is turned off after the
DEFAULT MESSAGE TIMEOUT
have been pressed and no target messages are active. When a keypress occurs or a target becomes active, the LCD
backlighting is turned on.
CURRENT CUT-OFF LEVEL: This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the
rated value) are very susceptible to noise. Some customers prefer very low currents to display as zero, while others
prefer the current be displayed even when the value reflects noise rather than the actual signal. The L30 applies a cut-
off value to the magnitudes and angles of the measured currents. If the magnitude is below the cut-off level, it is substi-
tuted with zero. This applies to phase and ground current phasors as well as true RMS values and symmetrical compo-
nents. The cut-off operation applies to quantities used for metering, protection, and control, as well as those used by
communications protocols. Note that the cut-off level for the sensitive ground input is 10 times lower that the
setting value. Raw current samples available via oscillography are not subject to cut-off.
CUT-OFF LEVEL
This setting does not affect the 87L metering cutoff, which is constantly at 0.02 pu.
VOLTAGE CUT-OFF LEVEL: This setting modifies the voltage cut-off threshold. Very low secondary voltage measure-
ments (at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed
as zero, while others prefer the voltage to be displayed even when the value reflects noise rather than the actual sig-
nal. The L30 applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below
the cut-off level, it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical
components. The cut-off operation applies to quantities used for metering, protection, and control, as well as those
used by communications protocols. Raw samples of the voltages available via oscillography are not subject cut-off.
The
CURRENT CUT-OFF LEVEL
power cut-off level is calculated as shown below. For Delta connections:
3-phase power cut-off
----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- -
=
For Wye connections:
3
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- -
3-phase power cut-off
=
per-phase power cut-off
where VT primary = VT secondary × VT ratio and CT primary = CT secondary × CT ratio.
For example, given the following settings:
: "0.02 pu"
CURRENT CUT-OFF LEVEL
: "1.0 V"
VOLTAGE CUT-OFF LEVEL
: "100 A"
PHASE CT PRIMARY
: "66.4 V"
PHASE VT SECONDARY
: "208.00 : 1"
PHASE VT RATIO
: "Delta".
PHASE VT CONNECTION
We have:
CT primary = "100 A", and
VT primary =
PHASE VT SECONDARY
The power cut-off is therefore:
power cut-off = (
CURRENT CUT-OFF LEVEL
= (
3
× 0.02 pu × 1.0 V × 100 A × 13811.2 V) / 66.4 V
= 720.5 watts
Any calculated power value below this cut-off will not be displayed. As well, the three-phase energy data will not accumu-
late if the total power from all three phases does not exceed the power cut-off.
GE Multilin
followed by the
and the
VOLTAGE CUT-OFF LEVEL
×
3
CURRENT CUT-OFF LEVEL
×
×
CURRENT CUT-OFF LEVEL
×
CURRENT CUT-OFF LEVEL
--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- -
=
x
PHASE VT RATIO
×
VOLTAGE CUT-OFF LEVEL
L30 Line Current Differential System
SCREEN SAVER FEATURE
SCREEN SAVER WAIT TIME
are used to determine the metered power cut-off levels. The
×
×
VT primary
VOLTAGE CUT-OFF LEVEL
VT secondary
×
VT primary
VOLTAGE CUT-OFF LEVEL
VT secondary
×
VT primary
VOLTAGE CUT-OFF LEVEL
VT secondary
= 66.4 V x 208 = 13811.2 V
× CT primary × VT primary)/VT secondary
5.2 PRODUCT SETUP
is "Enabled", the LCD backlighting
, providing that no keys
CURRENT
×
CT primary
(EQ 5.3)
×
CT primary
(EQ 5.4)
×
CT primary
(EQ 5.5)
5
5-25