5 SETTINGS
IEC61850-90-5 AGGREGATOR 1 CONFIGURATION
PMU AGGREGATOR1: NAME: A user-defined visible string of characters (max. 56) to identify the source of the
stream. This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the
IEC61850 MSVID filed in the output stream.
AGGREGATOR1: PHYSICAL PORT: This setting determines which physical ports through which the synchrophasor
traffic will be transmitted. The range is 1, 2, 3.
PMU AGGREGATOR1: UDP: This setting selects the UDP port number that is used by this dataset for network report-
ing. A default setting value for IEC 6150-90-5 is provided.
PMU AGGREGATOR1: #OF ASDUs: This setting sets the number of ASDU's per from 1 through to 4. Refer to the
table below.
Table 5–12: # OF ASDU
SETTINGS FOR # OF ASDU
1
2
3
4
m) CONTROL BLOCKS

PATH: SETTINGS
SYSTEM SETUP
 IEC 90-5 MSVCB
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MSVCB 1 SVENA: The SV Stream Control is set by either toggling an assigned FlexLogic operand or a remote client
write, to start and stop the streaming of R-SV frames. If remote client control is disabled, a negative response is pro-
vided to the client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that
GE Multilin
TRANSMISSION
ASDU at T0 (current values)
ASDU at T-1 (previous values) + ASDU at T0 (current values)
values)+ ASDU at T-2 (previous values) + ASDU at T-1 (previous ASDU at T0 (current
values)
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous
values)+ASDU at T0 (current values)
PHASOR MEASUREMENT UNIT
MSVCB 1 SVENA:
OFF
MSVCB 1 CLIENT CTRL:
OFF
MSVCB 1 SVENA DEFLT:
OFF
MSVCB 1 CONFREV:
1
MSVCB 1 PRIORITY:
4
MSVCB 1 IP CLASS:
46
MSVCB 1 VID:
0
MSVCB 1 APPID:
0
MSVCB 1 DEST. IP:
224.0.0.0
MSVCB 1 SECURITY:
0
L30 Line Current Differential System

IEC 90 – 5 MSVCB01 CONFIGURATION
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1 to 4294967295
Range: 0 to 7
Range: 0 to 252
Range: 0 to 4095
Range: 0 to 16383
Range: 0 to 255.255.255.255
Range: 0 to 2
5.4 SYSTEM SETUP
5
5-129