5 SETTINGS
c) PHASE OVERVOLTAGE (ANSI 59P, IEC PTOV)

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE
 OVERVOLTAGE1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The phase overvoltage element may be used as an instantaneous element with no intentional time delay or as a definite
time element. The input voltage is the phase-to-phase voltage, either measured directly from delta-connected VTs or as cal-
culated from phase-to-ground (wye) connected VTs. The specific voltages to be used for each phase are shown below.
GE Multilin
Figure 5–83: PHASE UNDERVOLTAGE1 SCHEME LOGIC
SETTING GROUP 1(6)
PHASE OV1
FUNCTION: Disabled
PHASE OV1 SIGNAL
SOURCE: SRC 1
PHASE OV1
PICKUP: 1.000 pu
PHASE OV1 PICKUP
DELAY:
1.00 s
PHASE OV1 RESET
DELAY:
1.00 s
PHASE OV1 BLOCK:
Off
PHASE OV1
TARGET: Self-reset
PHASE OV1
EVENTS: Disabled
L30 Line Current Differential System
5.6 GROUPED ELEMENTS


VOLTAGE ELEMENTS
PHASE OVERVOLTAGE1
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic Operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5
5-191