2.1.5.2
Settings
Addr.
Parameter
1103
FullScaleVolt.
1104
FullScaleCurr.
1105
Line Angle
1107
P,Q sign
1110
x'
1111
Line Length
1112
x'
1113
Line Length
1114
c'
1115
c'
1116
RE/RL(Z1)
1117
XE/XL(Z1)
1118
RE/RL(Z1B...Z5)
1119
XE/XL(Z1B...Z5)
1120
K0 (Z1)
1121
Angle K0(Z1)
1122
K0 (> Z1)
1123
AngleI K0(> Z1)
1126
RM/RL ParalLine
1127
XM/XL ParalLine
7SA522 Manual
C53000-G1176-C155-3
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
C
Setting Options
1.0 .. 1200.0 kV
10 .. 5000 A
30 .. 89 °
not reversed
reversed
0.0050 .. 9.5000 Ω/km
1A
0.0010 .. 1.9000 Ω/km
5A
0.1 .. 1000.0 km
0.0050 .. 15.0000 Ω/mi
1A
0.0010 .. 3.0000 Ω/mi
5A
0.1 .. 650.0 Miles
0.000 .. 100.000 µF/km
1A
0.000 .. 500.000 µF/km
5A
0.000 .. 160.000 µF/mi
1A
0.000 .. 800.000 µF/mi
5A
-0.33 .. 7.00
-0.33 .. 7.00
-0.33 .. 7.00
-0.33 .. 7.00
0.000 .. 4.000
-135.00 .. 135.00 °
0.000 .. 4.000
-135.00 .. 135.00 °
0.00 .. 8.00
0.00 .. 8.00
Default Setting
400.0 kV
Measurement: Full Scale
Voltage (100%)
1000 A
Measurement: Full Scale
Current (100%)
85 °
Line Angle
not reversed
P,Q operational measured
values sign
0.1500 Ω/km
x' - Line Reactance per
length unit
0.0300 Ω/km
100.0 km
Line Length
0.2420 Ω/mi
x' - Line Reactance per
length unit
0.0484 Ω/mi
62.1 Miles
Line Length
0.010 µF/km
c' - capacit. per unit line len.
µF/km
0.050 µF/km
0.016 µF/mi
c' - capacit. per unit line len.
µF/mile
0.080 µF/mi
1.00
Zero seq. comp. factor
RE/RL for Z1
1.00
Zero seq. comp. factor
XE/XL for Z1
1.00
Zero seq. comp.factor
RE/RL for Z1B...Z5
1.00
Zero seq. comp.factor
XE/XL for Z1B...Z5
1.000
Zero seq. comp. factor K0
for zone Z1
0.00 °
Zero seq. comp. angle for
zone Z1
1.000
Zero seq.comp.factor
K0,higher zones >Z1
0.00 °
Zero seq. comp. angle,
higher zones >Z1
0.00
Mutual Parallel Line comp.
ratio RM/RL
0.00
Mutual Parallel Line comp.
ratio XM/XL
2.1 General
Comments
57