Siemens SIPROTEC 7SA522 Manual page 540

Distance protection
Hide thumbs Also See for SIPROTEC 7SA522:
Table of Contents

Advertisement

A Appendix
Addr.
Parameter
3203A
Send Prolong.
3207A
Delay for alarm
3208
Release Delay
3209A
TrBlk Wait Time
3210A
TrBlk BlockTime
3401
AUTO RECLOSE
3402
CB? 1.TRIP
3403
T-RECLAIM
3404
T-BLOCK MC
3406
EV. FLT. RECOG.
3407
EV. FLT. MODE
3408
T-Start MONITOR
3409
CB TIME OUT
3410
T RemoteClose
3411A
T-DEAD EXT.
3420
AR w/ DIST.
3421
AR w/ SOTF-O/C
3422
AR w/ W/I
3423
AR w/ EF-O/C
3424
AR w/ DTT
3425
AR w/ BackUpO/C
3430
AR TRIP 3pole
3431
DLC or RDT
3433
T-ACTION ADT
3434
T-MAX ADT
3435
ADT 1p allowed
3436
ADT CB? CLOSE
3437
ADT SynRequest
3438
T U-stable
3440
U-live>
3441
U-dead<
3450
1.AR: START
3451
1.AR: T-ACTION
3453
1.AR Tdead 1Flt
3454
1.AR Tdead 2Flt
3455
1.AR Tdead 3Flt
3456
1.AR Tdead1Trip
3457
1.AR Tdead3Trip
540
Function
C
Setting Options
Teleprot. E/F
0.00 .. 30.00 sec
Teleprot. E/F
0.00 .. 30.00 sec
Teleprot. E/F
0.000 .. 30.000 sec
0.00 .. 30.00 sec; ∞
Teleprot. E/F
Teleprot. E/F
0.00 .. 30.00 sec
Autoreclosure
OFF
ON
Autoreclosure
YES
NO
Autoreclosure
0.50 .. 300.00 sec
Autoreclosure
0.50 .. 300.00 sec; 0
Autoreclosure
with PICKUP
with TRIP
Autoreclosure
blocks AR
starts 3p AR
Autoreclosure
0.01 .. 300.00 sec
Autoreclosure
0.01 .. 300.00 sec
0.00 .. 300.00 sec; ∞
Autoreclosure
0.50 .. 300.00 sec; ∞
Autoreclosure
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
Autoreclosure
NO
Autoreclosure
WITHOUT
RDT
DLC
0.01 .. 300.00 sec; ∞
Autoreclosure
Autoreclosure
0.50 .. 3000.00 sec
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
YES
NO
Autoreclosure
0.10 .. 30.00 sec
Autoreclosure
Autoreclosure
30 .. 90 V
Autoreclosure
Autoreclosure
2 .. 70 V
Autoreclosure
Autoreclosure
YES
NO
0.01 .. 300.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
0.01 .. 1800.00 sec; ∞
Autoreclosure
Default Setting
0.05 sec
Time for send signal prolongation
10.00 sec
Unblocking: Time Delay for Alarm
0.000 sec
Time Delay for release after pickup
0.04 sec
Transient Block.: Duration external
flt.
0.05 sec
Transient Block.: Blk.T. after ext. flt.
ON
Auto-Reclose function
NO
CB ready interrogation at 1st trip
3.00 sec
Reclaim time after successful AR
cycle
1.00 sec
AR blocking duration after manual
close
with TRIP
Evolving fault recognition
starts 3p AR
Evolving fault (during the dead
time)
0.20 sec
AR start-signal monitoring time
3.00 sec
Circuit Breaker (CB) Supervision
Time
∞ sec
Send delay for remote close
command
∞ sec
Maximum dead time extension
YES
AR with distance protection
YES
AR with switch-onto-fault overcur-
rent
YES
AR with weak infeed tripping
YES
AR with earth fault overcurrent
prot.
YES
AR with direct transfer trip
YES
AR with back-up overcurrent
YES
3pole TRIP by AR
WITHOUT
Dead Line Check or Reduced
Dead Time
0.20 sec
Action time
5.00 sec
Maximum dead time
NO
1pole TRIP allowed
NO
CB ready interrogation before re-
closing
NO
Request for synchro-check after
3pole AR
0.10 sec
Supervision time for dead/ live
voltage
48 V
Voltage threshold for live line or
bus
30 V
Voltage threshold for dead line or
bus
YES
Start of AR allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
1.20 sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
Comments
7SA522 Manual
C53000-G1176-C155-3