4 Technical Data
- for rated voltages
- for rated voltages
- for rated voltages
Current consumption, energized
Maximum admissible voltage
Impulse filter on output
Binary Outputs
Signalling / Command Relays (see also terminal assignments in Appendix A)
Quantity and Data
Order Variant
7SA522-*A/E/J
7SA522-*C/G/L
7SA522-*N/Q/S
7SA522-*D/H/M
7SA522-*P/R/T
Switching capability
Switching voltage
DC
AC
Permissible current per contact (continuous)
Permissible current per contact (close and
hold) / pulse current
Total current on common path
Operating time, approx.
1
Alarm relay
)
Switching capability
Switching voltage
Permissible current per contact
1
) UL-listed with the following nominal values:
434
24/48 VDC
60/110/125 VDC
110/125/220/250 VDC
220/250 VDC
approx. 1.8 mA
independent of the control voltage
300 VDC
220 nF coupling capacitance at 220 V with recovery time >
60 ms
UL-listed
NO Contact
(normal)
x
7
x
14
x
7
x
21
x
14
MAKE
1000 W/VA
BREAK
30 W/VA
40 W resistive
25 W at L/R ≤ 50 ms
8 ms
with 1 NC contact or 1 NO contact (switchable)
MAKE
1000 W/VA
BREAK
30 W/VA
40 W resistive
25 W at L/R ≤ 50 ms
250 V
5 A continuous;
30 A for 0.5 s
According to the Order Variant (allocatable)
NO Contact
1
1
)
(fast)
)
7
7
10
7
10
250 V
250 V
5 A
30 A for 0.5 s (NO contact)
5 A continuous
30 A for 0.5 s
5 ms
≥ 19 VDC (pu =
U
pu
pickup)
≤ 14 VDC (do =
U
do
dropout)
≥ 88 VDC
U
pu
≤ 66 VDC
U
do
≥ 176 VDC
U
pu
≤ 117 VDC
U
do
NO or NC
NO contact
1
(selectable)
)
(high-speed)
1
-
2
-
1
5
3
-
2
5
1000 W/VA
1000 W/VA
200 V (max.)
8 ms
1 ms
7SA522 Manual
C53000-G1176-C155-3
1
)